99
SS Programming Example
U
SER
G
UIDE
PROGRAMMI
NG AND CONFIGURATION EXAMPLES
SMART-S
ENSOR
™
2004 – 2014 Reliable Controls
®
Corporation. All rights reserved.
9
If necessary, click the Setup button of the
SMART-Sensor
worksheet to open
the
SMART-Sensor Setup
dialog box.
F
IGURE
91: SMART-S
ENSOR
S
ETUP
DIALOG
BOX
FUNCTIONS
Complete the programming of the SS by performing the following tasks:
•
Enter a calibration value for the onboard temperature sensor ± 3.1
degrees,
•
Enter a calibration value for the onboard relative humidity sensor on -H
models ± 31%,
•
If desired, enable the display of the secondary point on the top row in
Idle
mode,
•
If the secondary point is enabled, a two-character descriptive
abbreviation may be programmed to be displayed together with the
value,
•
Disable the onboard configuration tools for addressing and airflow
calibration, and
•
Enter a descriptive name for the SS that will appear to uniquely identify
the SS in the SMART-Sensors node of the
System Tree
.
10
Verify that SS setup changes have taken effect and that the SS and mapped
points are operating properly.
11
Close the
SMART-Sensor
worksheet.
12
As a suggested best practice, backup the
pan
file to save changes to the RC-
Studio
®
2.0 project database.
All values that must be modifiable by the SS, including both onboard options and/or
operator modification will have to be configured for
Can Change
.