![Reliable Controls SS-CO2-H-UD Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/reliable-controls/ss-co2-h-ud/ss-co2-h-ud_user-manual_1436213037.webp)
28
2004 – 2014 Reliable Controls
®
Corporation. All rights reserved.
I
NSTALLING
O
NE
SSX E
XPANSION
B
OARD
T
O
INSTALL
AND
CONFIGURE
ONE
SSX
EXPANSION
BOARD
1
Configure the SSX expansion board jumpers as required (EOL jumpers,
network jumpers, and the power jumper).
2
Connect a rollover Voice Cable (SS-VC) from the host controller to the SMART-
Net
™
port on the SSX.
3
Connect the first SS to any of the PROG SENS ports on the SSX using a rollover
SS-VC.
4
Connect the second and subsequent SSs to the first SS using straight-through
Data Cables (SS-DC) between each SS.
5
Repeat steps 3 and 4 for the remaining SSs to be connected to the SSX.
Each SSX expansion board supports up to a maximum of 16 SSs. The use of an SSX
expansion board does not expand the maximum number of SSs supported by a specific
controller. Refer to Table 4 for the maximum number of SSs supported by each Reliable
Controls
®
MACH-System controller.