8
REGULUS - STDC E Controller - www.regulus.eu
Mind the cables in order to prevent unintentional pressing the clamps.
Caution
Caution
C 3 - Installing the temperature sensors
The controller operates with Pt1000 temperature sensors.
Max. S1 sensor lead length is 30 m with its cross section at least 0,75 mm
2
.
Max. S2 and S3 sensor lead length is 10 m with its cross section at least0,75 mm
2
.
No contact resistance is permitted in the conductive connection to sensors!
The temperature sensor cables must be routed separately from mains voltage cables!
Danger