REGULUS - STDC E Controller - www.regulus.eu

F 6.4 - Collector protection (solar only)

Collector protection prevents overheating of the collector. The pump is switched on to transfer heat from the 
collector to the storage tank.
If 

„CP Ton”

 is exceeded at the collector sensor, the pump is switched on until the temperature reaches 

„CP 

Toff”

 or the temperature 

„CP Tmax storage”

 is exceeded in the storage or pool.

Collector protection - Setting range: On, Off / default setting: Off
CP Ton settings range: 60 °C to 150 °C / Default: 110 °C
CP Toff settings range: 50 °C to Ton minus 10 °C / Default: 100 °C
CP Tmax storage settings range: 0 °C to 140 °C / Default: 90 °C

When collector protection is active, the storage or pool may get heated to a very high temperature!

F 6.5 - Col.- Alarm (solar only)

If this temperature is exceeded at the collector sensor when the solar pump is on, a warning is triggered and 
a warning message is shown in the display.

Collector alarm settings range: on / off / Default: off
Col. alarm - setting range: 60 °C to 300 °C / Default: 150 °C

F 6.6 - Recooling (solar only)

At the end of a sunny day the temperature in a storage tank may easily reach high values. In order to prevent 
further temperature increase the next day, excess energy can be released into the air via collectors under 
cloudy conditions or after sunset.
If the temperature in the storage tank exceeds the value 

„Recooling Tset”

 and the collector is at least by 

20 °C cooler than the storage tank, the solar pump starts. The storage tank is then cooled down until the 

„Recooling Tset”

 is reached. 

Setting range: Recooling off, on / default setting: off
Setting range: Recooling Tset from 0 °C to 99 °C / default setting: 70 °C

 

This function causes energy loss via the collector! It may be combined e.g. with the System 
protection function (F 6.3) that causes collector overheating. It is also useful during holiday 
absence when no heat is used.

F 6.7 - Anti-Legionella

With the 

“AL function”

 activated the STDC makes it possible to heat the storage tank up to a higher 

temperature (

“AL Tsetpoint S2”

, provided that the energy source allows this. Time periods where the AL 

heat up is attempted are to be setup in the menu 

“AL times”

 Once the temperature 

“AL Tset S2”

 is reached, 

the controller will try to maintain this temperature for the time period set in 

“AL residence time”

. When this 

happened, the time and date is saved and displayed in the menulog 

“AL heat”

.

AL Function settings range: on / off / Default: off
AL Tset S2 (Thermostat uses both S1 and S2) settings range: 60°C to 99°C / default setting: 70°C
AL residence time - settings range: 1 to 60 minutes / default setting: 15 minutes
AL heat. (no setting): Displays the date and time of the last successful AL heat up
AL times - settings range: Mo-Su , 0-24h/ default setting: daily 3-5h

The anti-Legionella function is switched off at delivery. 

For solar systems:

 This function may be 

used for storage tanks with installed S2 sensor only. After each successful performance of AL 
function, a message with performance date will appear on the display. 

For Thermostat function:

 

S1 sensor is used for switching off. If both the sensors (S1 and S2) are connected, then both have 
to reach the Legionella temperature 

“T Legionela S2”

.

During the anti-Legionella function the storage tank is heated up over the set value 

„Tmax S2”

.

This anti-Legionella function does not provide complete protection against Legionella, because the controller is 

dependent on suf

fi

cient energy being fed in, and it is not possible to monitor the temperatures in the 

entire range of the storage tanks and the connected piping system. To provide complete protection 
against Legionella bacteria, it must be ensured that the temperature is raised to the necessary 
value, and at the same time there must be water circulation in the storage tanks.

Danger

Caution

Caution

Danger

Danger

Содержание STDC E

Страница 1: ...EN v 1 5 STDC E Controller Instruction Manual...

Страница 2: ...boiler with storage tank 10 D 4 Heat transfer between storage tanks 10 D 5 Return line preheating 11 D 6 Thermostat 11 D 7 Universal T 12 D 8 Stop valve 12 D 9 Solar thermal system with heat exchange...

Страница 3: ...of the entire solar system It is forbidden to tamper with the Controller with the exception of a written consent from the Manufacturer It is forbidden to install any additional components into the Co...

Страница 4: ...erature sensors for immersion sleeves 2 screws 3 5 35 mm and 2 plugs 6 mm for wall installation 4 strain relief clips with 8 screws 1 terminal block for PE replacement fuse 2A slow blow Instruction Ma...

Страница 5: ...urn line preheating 6 B 6 Thermostat 7 B 7 Universal T 8 B 8 Stop valve 9 B 9 Solar thermal system with heat exchanger and swimming pool 8 Stop valve 9 Sol rn syst m s tepeln m v m n kem a baz nem Hea...

Страница 6: ...t of the housing up to the selected position and mark the 2 mounting holes Make sure that the wall surface is as even as possible so that the housing does not become distorted when it is screwed on 5...

Страница 7: ...installed for switching off the controller Caution C 2 Electrical wiring Wiring instructions 1 Make sure the circuit breaker is in off position and power supply is off 2 Select a suitable hydraulic sc...

Страница 8: ...controller operates with Pt1000 temperature sensors Max S1 sensor lead length is 30 m with its cross section at least 0 75 mm2 Max S2 and S3 sensor lead length is 10 m with its cross section at least...

Страница 9: ...tor N R pump L N pump N R NC contact PE protective conductor green yellow D 2 Solar thermal system with swimming pool Sensor connection max 12V Terminal connection for S1 2 sensor 1 collector S2 2 sen...

Страница 10: ...protective conductor green yellow D 4 Heat transfer between storage tanks Sensor connection max 12V Terminal connection for S1 2 sensor 1 storage tank S2 2 sensor 2 storage tank S3 2 sensor 3 free The...

Страница 11: ...y valve on the return line relay R off valve closed flow direction AB B no backup heating relay R on valve open flow direction AB A flow through the storage tank D 6 Thermostat Sensor connection max 1...

Страница 12: ...is higher than the temperature at sensor 2 relay R switches turning pump on D 8 Stop valve Sensor connection max 12V Terminal connection for S1 2 sensor 1 heating line S2 2 sensor 2 storage tank S3 2...

Страница 13: ...ensor 1 solar collector S2 2 sensor 2 pool S3 2 sensor 3 pool water circuit The polarity of the sensors is freely selectable V1 0 10V or PWM Mains voltage 230V 50Hz Terminal connection for L mains pha...

Страница 14: ...r the changes which have been made should be saved The function of each of the other three keys is shown in the display line directly above the keys the right hand key 4 generally has a confirmation a...

Страница 15: ...ould be used to test the switch outputs with the consumers connected and to check the sensor values for plausibility Then switch on automatic mode Read the explanations for the individual parameters o...

Страница 16: ...e values with explanations 2 Function control of the system with operating hours etc 3 Select graphics mode or overview mode 4 Automatic mode manual mode or switch unit off 5 Set parameters needed for...

Страница 17: ...sc exits the Info mode If Error appears on the display instead of the measurement value then there may be a defective or improper temperature sensor If the cables are too long or the sensors are not p...

Страница 18: ...are available day year F 2 2 Average temperature difference T Display of the average temperature difference between the reference sensors of the solar system with the consumer switched on F 2 3 Heat o...

Страница 19: ...es and operating states of the connected consumers F 3 2 Overview In overview mode the measured temperatures and operating states of the connected consumers are shown in text form F 3 3 Alternating In...

Страница 20: ...cted F 4 2 Manual The relay and thus the connected consumer are switched on and off by pressing a key with no regard to the current temperatures and the parameters which have been set The measured tem...

Страница 21: ...e again then the pump and or the valve are switched off again Setting range 0 99 C for hydraulic variants Thermostat and Universal T this value may be set to Off Default setting 60 C for hydraulic var...

Страница 22: ...in Setting range 0 99 C for hydraulic variants Thermostat and Universal T this value may be set to Off Default setting 60 C for hydraulic variant Solar system with pool the default setting is off Temp...

Страница 23: ...drops further to the set value Frost stage 2 the controller switches the pump on continuously If the collector temperature then exceeds the value Frost stage 2 by 2 C the pump switches off again Frost...

Страница 24: ...overheating It is also useful during holiday absence when no heat is used F 6 7 Anti Legionella With the AL function activated the STDC makes it possible to heat the storage tank up to a higher temper...

Страница 25: ...V pumps on output R1 Use this setting for standard pump only PWM 0 10V outputs are switched off 0 10V Speed control for special pumps via low energy pump output V1 by means of a 0 10V Relay output R1...

Страница 26: ...ng 10 0V Heating 0 0 to 5 0V Default setting 0 0V F 7 2 6 0 10V Max This determines the output signal for the highest speed of the pump that is used e g during purging or manu al operation Setting ran...

Страница 27: ...p is switched off Mode V2 Speed control set to T starts from the min speed After the purging time at min speed the controller switches to the set min speed If the temperature differ ence T between the...

Страница 28: ...min F 7 3 4 Max speed The maximum speed of the pump is specified here Setting range 70 to 100 Default setting 100 The indicated percentages are guide values that may vary to a greater or lesser extent...

Страница 29: ...ns for the individual parameters in these instructions and check whether further settings are necessary for your application F 7 7 Factory settings All of the settings that have been made can be reset...

Страница 30: ...the sensor is often not at the hottest location When the start help is activated the following sequence is carried out If the temperature at the collector sensor increases by the value specified unde...

Страница 31: ...or selecting Exit menu lock The menus listed below remain completely accessible despite the menu lock being activated and can be used to make adjustments if necessary F 1 Measurements F 2 Statistics F...

Страница 32: ...issioning The choice of languages may differ however depending on the device design Language selection is not available in every device design The latest version contains the following languages Germa...

Страница 33: ...than 6 times in 5 minutes Restart Means that the controller was restarted for example due to a power failure Check the date and time G 2 Replacing the fuse Repairs and maintenance may only be perform...

Страница 34: ...OPEAN DIRECTIVE 2002 96 ES European Directive 2002 96 EC requires that the equipment bearing this symbol on the product and or its packaging must not be disposed of with unsorted municipal waste The s...

Страница 35: ......

Страница 36: ...01 2017 REGULUS spol s r o Do Kout 1897 3 http www regulus eu 143 00 Praha 4 E mail sales regulus cz...

Отзывы: