F 7.3 - Speed control R1

If the speed control is activated, the STDC E makes it possible to vary the speed of standard pumps at relay 
by means of special internal electronics.

This function should only be activated by a specialist. Depending on the pump and pump stage 
used, the minimum speed should not be set too low, because otherwise the pump or the system 
may be damaged. The information provided by the relevant manufacturer must also be observed! If 
in doubt, the min. speed and the pump stage should generally be set too high rather than too low. 

F 7.3.1 - Speed control mode

Off:

 There is no speed control. The connected pump is only switched on or off with full speed.

Mode V1:

 Speed control set to 

Δ

T, starts from the max. speed:  

After the purging time (at max. speed) the controller switches to the set max. speed. If the temperature 
difference 

Δ

T between the reference sensors (collector and storage tank) is smaller than the set value, then 

the speed is decreased by one step after the Sweep time expires. If the temperature difference between the 
reference sensors is greater than the set value, then the speed is increased by one step after the Sweep time 
expires. If the controller has adjusted the speed of the pump down to the smallest stage and the 

Δ

T between 

the reference sensors is below the desired 

Δ

T off, the pump is switched off. 

Mode V2:

  Speed control set to 

Δ

T, starts from the min. speed.  

After the purging time (at min. speed) the controller switches to the set min. speed. If the temperature differ-
ence 

Δ

T between the reference sensors (collector and storage tank) is greater than the set value, then the 

speed is increased by one step after the Sweep time expires. If the temperature difference 

Δ

T between the 

reference sensors is below the set value, then the speed is decreased by one step after the Sweep time ex-
pires. If the controller has adjusted the speed of the pump down to the smallest stage and the 

Δ

T between the 

reference sensors is below the desired T

Δ

off, the pump is switched off. 

Mode V3:

 Speed control set to a constant collector temperature, starts from the min. speed.

After the purging time (at min. speed) the controller switches to the set min. speed. If the temperature at the 
reference sensor (collector, in systems with heat exchanger on relay 2 the heat exchanger instead) is great-
er than the setpoint to be set subsequently, then the speed is increased by one step after the Sweep time 
expires. If the temperature at the reference sensor (collector) is less than the setpoint to be set subsequently, 
then the speed is decreased by one step after the Sweep time expires.

Setting range: V1,V2,V3, off/default setting: off

F 7.2.8.b - Technical data for PWM and 0-10V

PWM: 20% to 100%, 1kHz
Designed for a load of 
10K Ohm

Technical data PWM:

Technical data 0-10V:

0-10V:  2V to 10V (20% to 100%)
Designed for a load of 10K Ohm.

10V = 100% Speed
5V = 50% Speed
2V = 20% Speed
0V = Off

Danger

Содержание STDC E

Страница 1: ...EN v 1 5 STDC E Controller Instruction Manual...

Страница 2: ...boiler with storage tank 10 D 4 Heat transfer between storage tanks 10 D 5 Return line preheating 11 D 6 Thermostat 11 D 7 Universal T 12 D 8 Stop valve 12 D 9 Solar thermal system with heat exchange...

Страница 3: ...of the entire solar system It is forbidden to tamper with the Controller with the exception of a written consent from the Manufacturer It is forbidden to install any additional components into the Co...

Страница 4: ...erature sensors for immersion sleeves 2 screws 3 5 35 mm and 2 plugs 6 mm for wall installation 4 strain relief clips with 8 screws 1 terminal block for PE replacement fuse 2A slow blow Instruction Ma...

Страница 5: ...urn line preheating 6 B 6 Thermostat 7 B 7 Universal T 8 B 8 Stop valve 9 B 9 Solar thermal system with heat exchanger and swimming pool 8 Stop valve 9 Sol rn syst m s tepeln m v m n kem a baz nem Hea...

Страница 6: ...t of the housing up to the selected position and mark the 2 mounting holes Make sure that the wall surface is as even as possible so that the housing does not become distorted when it is screwed on 5...

Страница 7: ...installed for switching off the controller Caution C 2 Electrical wiring Wiring instructions 1 Make sure the circuit breaker is in off position and power supply is off 2 Select a suitable hydraulic sc...

Страница 8: ...controller operates with Pt1000 temperature sensors Max S1 sensor lead length is 30 m with its cross section at least 0 75 mm2 Max S2 and S3 sensor lead length is 10 m with its cross section at least...

Страница 9: ...tor N R pump L N pump N R NC contact PE protective conductor green yellow D 2 Solar thermal system with swimming pool Sensor connection max 12V Terminal connection for S1 2 sensor 1 collector S2 2 sen...

Страница 10: ...protective conductor green yellow D 4 Heat transfer between storage tanks Sensor connection max 12V Terminal connection for S1 2 sensor 1 storage tank S2 2 sensor 2 storage tank S3 2 sensor 3 free The...

Страница 11: ...y valve on the return line relay R off valve closed flow direction AB B no backup heating relay R on valve open flow direction AB A flow through the storage tank D 6 Thermostat Sensor connection max 1...

Страница 12: ...is higher than the temperature at sensor 2 relay R switches turning pump on D 8 Stop valve Sensor connection max 12V Terminal connection for S1 2 sensor 1 heating line S2 2 sensor 2 storage tank S3 2...

Страница 13: ...ensor 1 solar collector S2 2 sensor 2 pool S3 2 sensor 3 pool water circuit The polarity of the sensors is freely selectable V1 0 10V or PWM Mains voltage 230V 50Hz Terminal connection for L mains pha...

Страница 14: ...r the changes which have been made should be saved The function of each of the other three keys is shown in the display line directly above the keys the right hand key 4 generally has a confirmation a...

Страница 15: ...ould be used to test the switch outputs with the consumers connected and to check the sensor values for plausibility Then switch on automatic mode Read the explanations for the individual parameters o...

Страница 16: ...e values with explanations 2 Function control of the system with operating hours etc 3 Select graphics mode or overview mode 4 Automatic mode manual mode or switch unit off 5 Set parameters needed for...

Страница 17: ...sc exits the Info mode If Error appears on the display instead of the measurement value then there may be a defective or improper temperature sensor If the cables are too long or the sensors are not p...

Страница 18: ...are available day year F 2 2 Average temperature difference T Display of the average temperature difference between the reference sensors of the solar system with the consumer switched on F 2 3 Heat o...

Страница 19: ...es and operating states of the connected consumers F 3 2 Overview In overview mode the measured temperatures and operating states of the connected consumers are shown in text form F 3 3 Alternating In...

Страница 20: ...cted F 4 2 Manual The relay and thus the connected consumer are switched on and off by pressing a key with no regard to the current temperatures and the parameters which have been set The measured tem...

Страница 21: ...e again then the pump and or the valve are switched off again Setting range 0 99 C for hydraulic variants Thermostat and Universal T this value may be set to Off Default setting 60 C for hydraulic var...

Страница 22: ...in Setting range 0 99 C for hydraulic variants Thermostat and Universal T this value may be set to Off Default setting 60 C for hydraulic variant Solar system with pool the default setting is off Temp...

Страница 23: ...drops further to the set value Frost stage 2 the controller switches the pump on continuously If the collector temperature then exceeds the value Frost stage 2 by 2 C the pump switches off again Frost...

Страница 24: ...overheating It is also useful during holiday absence when no heat is used F 6 7 Anti Legionella With the AL function activated the STDC makes it possible to heat the storage tank up to a higher temper...

Страница 25: ...V pumps on output R1 Use this setting for standard pump only PWM 0 10V outputs are switched off 0 10V Speed control for special pumps via low energy pump output V1 by means of a 0 10V Relay output R1...

Страница 26: ...ng 10 0V Heating 0 0 to 5 0V Default setting 0 0V F 7 2 6 0 10V Max This determines the output signal for the highest speed of the pump that is used e g during purging or manu al operation Setting ran...

Страница 27: ...p is switched off Mode V2 Speed control set to T starts from the min speed After the purging time at min speed the controller switches to the set min speed If the temperature differ ence T between the...

Страница 28: ...min F 7 3 4 Max speed The maximum speed of the pump is specified here Setting range 70 to 100 Default setting 100 The indicated percentages are guide values that may vary to a greater or lesser extent...

Страница 29: ...ns for the individual parameters in these instructions and check whether further settings are necessary for your application F 7 7 Factory settings All of the settings that have been made can be reset...

Страница 30: ...the sensor is often not at the hottest location When the start help is activated the following sequence is carried out If the temperature at the collector sensor increases by the value specified unde...

Страница 31: ...or selecting Exit menu lock The menus listed below remain completely accessible despite the menu lock being activated and can be used to make adjustments if necessary F 1 Measurements F 2 Statistics F...

Страница 32: ...issioning The choice of languages may differ however depending on the device design Language selection is not available in every device design The latest version contains the following languages Germa...

Страница 33: ...than 6 times in 5 minutes Restart Means that the controller was restarted for example due to a power failure Check the date and time G 2 Replacing the fuse Repairs and maintenance may only be perform...

Страница 34: ...OPEAN DIRECTIVE 2002 96 ES European Directive 2002 96 EC requires that the equipment bearing this symbol on the product and or its packaging must not be disposed of with unsorted municipal waste The s...

Страница 35: ......

Страница 36: ...01 2017 REGULUS spol s r o Do Kout 1897 3 http www regulus eu 143 00 Praha 4 E mail sales regulus cz...

Отзывы: