installation
32 | Grandview
®
G800C-1 Gas Fireplace
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible
materials are not adhered to. It is of greatest
importance that this fireplace and vent system be
installed only in accordance with these instructions.
Outside Finish Installation (Non Cool Wall) - Clearances
The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
Minimum Vent Clearances
to Combustibles
Outside Finish Clearance Requirements
Clearance:
Dimension
Measured From:
A: Mantel Height (min.)
10" (254 mm)
Top of Fireplace Opening
B: Sidewall
25" (635 mm) one side only
Side of Fireplace Opening
C: Ceiling
36-1/2" (927 mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
12" (305 mm)
Top of Fireplace Opening
E: Alcove Width
84" (2134 mm)
Wall to Wall (Minimum)
F: Alcove Depth
36" (914 mm)
Front to Back Wall (Maximum)
Notes:
0"
No Hearth Required
Horizontal Top
2" (51 mm)
Horizontal Side
1-1/2 " (38 mm)
Horizontal Bottom
1-1/2" (38 mm)
Vertical Vent
1-1/2" (38 mm)
Alcove
E
F
C
D
A
E
F