Regency Excalibur
®
P90E-11 Direct Vent Gas Stove
| 19
installation
Fireplace
Stand
No hearth is
required when
the unit is raised
3" (76mm) off of
the floor surface
Floorin
g
Hearth Requirements
Floor Mounted Fireplaces
Raised Fireplaces
Facing Requirement
This fireplace requires a non-combustible material extending from the
framing header and sides.
The flanges on the front face of the fireplace are for a facing thickness
of 3-3/8" (86mm).
Facing Over 3-3/8" (86mm) Thick
If the facing material is over 3-3/8" (86mm) thick (example: brick or river rock),
install the facing around the perimeter of the face. You may wish to make a
face template as shown on the diagram.
Note:The template should be slightly larger than the actual surround itself to
accommodate the removal of the surround when having this serviced. The
surround when fitted must be lifted up and out in order to remove it.
Regency provides a template
on the box.
NOTE: If using a brick hearth,
the fireplace will need to be
raised to accommodate the brick
thickness. Example: If the brick is
2" thick, the unit must be raised 1".
Note: 4 8 " ( 1 2 1 9 m m )
is the minimum
height for both
flex termination or
Rigid Pipe venting.
4. Note: The unit does not
have to be completely
enclosed in a chase. The
clearance on top of the
unit is 0" to the standoffs
so combustible building
materials can be laid
directly on top of the
standoffs. You must
maintain clearance from
the vent to combustible
materials for both
rigid and flex, see the
"Clearances" section.
You must take into account
the depth of the floor covering
(carpet, tile, linoleum, etc.)
when determining the height
of the fireplace stand.
The
HeatWave
Duct Kit has different
clearance and framing requirements, check
the
HeatWave
manual for details.
Please note that all vertical measurements are taken from the
base of the unit
excluding
risers or bottom stand-offs.