background image

 

Regency

®

 CLASSIC™ C34E-11 Direct Vent Freestanding Gas Stove

  |    

33

installation

Diagram 9

Determine  if  ceiling 

joists, roof rafters 

or 

other  framing 
will obstruct the 
venting  system. 
You  may  wish 
to  relocate  the 
appliance  or  to 
offset, as shown 

i n 

D i a g r a m   9 

t o 

avoid  cutting 
load  bearing 
members.

3.

  To install the Round Support Box/Wall Thim-

ble in a flat ceiling, cut a 10 inch square hole 
in the ceiling centered on the hole drilled in 
Step 2. Frame the hole as shown in Diagram 
10.

Diagram 8

Diagram 10

VERTICAL  
TERMINATION

1.  Maintain the 1-1/4" clearances (air spaces) 

to combustibles when passing through ceil-

Diagram 7

Diagram 6

Diagram 5

4.  Attach the Vinyl Siding Standoff (if required) 

to the Horizontal Vent Termination, but first 
run a bead of non-hardening mastic around 
its  outside  edges,  so  as  to  make  a  seal 
between vent cap and the standoff. Install 
the Vinyl Siding Standoff  between the vent 
cap and the exterior wall and attach with the 
four  wood  screws  provided.  Seal  around 
the Vinyl Siding Standoff on all four sides. 
Diagram 5.   

The arrow on the vent cap 

should be pointing up.

  Insure  that  the 

1-1/4" clearances to combustible materials 
are maintained. See Diagram 5.

Note:  If installing termination on a siding 

covered wall, a vinyl siding standoff or 

furring strips must be used to ensure 

that the termination is not recessed 

into the siding. The four wood screws 

provided should be replaced with ap-

propriate fasteners for stucco, brick, 

concrete, or other types of sidings.

5.  Before connecting the horizontal run of vent 

pipe to the vent termination, slide the black 
decorative wall thimble cover over the vent 
pipe, then slide the Wall Thimble over the 
vent pipe.

6.  Slide  the  appliance  and  vent  assembly 

towards  the  wall  carefully  inserting  the 
vent pipe into the vent cap assembly. It is 
important  that  the  vent  pipe  extends  into 
the vent cap a sufficient distance so as to 
result in a minimum pipe overlap of 1-1/4 
inches. Secure the connection between the 
vent pipe and the vent cap by attaching the 
two sheet metal strips extending from the 
vent cap assembly into the outer wall of the 
vent pipe. Use the two sheet metal screws 
provided to connect the strips to the pipe 
section. Bend any remaining portion of the 
sheet metal strip back towards the vent  cap, 
so it will be concealed by the decorative wall 
thimble cover. See Diagram 6.

7.  Install Wall Thimble in the center of the 10" 

square  and  attach  with  wood  screws  (in 
Canada).

8.  Slide the decorative wall thimble up to the 

wall surface being careful not to scratch the 
paint and attach with screws provided. Apply 
decorative brass or chrome trim if desired.   
See Diagram 7.

ings, walls, roofs, enclosures, 
attic  rafter,  or  other  nearby 
combustible surfaces.

 

Do not pack air spaces with 
insulation.  Check  "Venting 
Arrangements"  section  for 
the maximum vertical rise of 
the venting system and the 
maximum  horizontal  offset 
limitations.

2.  Set  the  gas  appliance  in 

its  desired  location.  Drop  a 
plumb  bob  down  from  the 
ceiling to the position of the 
appliance flue exit, and mark 
the location where the vent 
will  penetrate  the  ceiling. 
Drill a small hole at this point. 
Next, drop a plumb bob from 
the roof to the hole previously 
drilled in the ceiling, and mark 
the spot where the vent will 
penetrate the roof. 

Diagram 11: The upper half of the flashing is 

installed under the roofing material and not 

nailed down until the chimney is installed. This 

allows for small adjustments.

4.

  Assemble the desired lengths of black pipe 

and  elbows necessary to reach from the 
appliance  adaptor  up  though  the  Round 
Support Box. Ensure that all pipes and el-
bow connections are in the fully twist-locked 
position and sealed.

5.

  Cut a hole in the roof centered on the small 

drilled hole placed in the roof in Step 2. The 
hole  should  be  of  sufficient  size  to  meet 
the  minimum  requirements  for  clearance 
to combustibles of 1-1/4". Slip the flashing 
under the shingles (shingles should overlap 
half the flashing) as per Diagram 11.

6.

  Continue to assemble pipe lengths.

Note:

 If an offset is necessary in the attic to 

avoid obstructions, it is important to support 
the vent pipe every 3 feet, to avoid exces-
sive  stress  on  the  elbows,  and  possible 
separation.   Wall  straps  are  available  for 
this purpose.  See Diagram 9. 

Содержание Classic C34E

Страница 1: ...r s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or th...

Страница 2: ...as been designed to provide you with all the warmth and charm of a woodstove at the flick of a switch The models C34E NG11 and C34E LP11 of this series have been approved by Intertek for both safety a...

Страница 3: ...ND PILOT LIGHT SEVEN DAY SAFETY TIMER Important information if using the appliance in CPI continuous pilot mode only This appliance is a ProFlame 2 system fitted with the On Demand Pilot a safety feat...

Страница 4: ...C34E 11 Direct Vent Freestanding Gas Stove dimensions 28 711mm ALL PICTURES DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENT...

Страница 5: ...Systems for Residential Manufactured and Mobile Homes 27 DV Stove Horizontal Vent Kit 29 DV Stove Horizontal Vent Kit Installation 29 Dura Vent Termination Kit 31 owner s information installer s info...

Страница 6: ...AN CSA Z240 VC V hicules de camping ou la norme 24 CFR Part 3280 Manufactured Home Construction and Safety Standard Si ces normes ne sont pas pertinentes utilisez la norme ANSI NCSBCS A225 1 NFPA 501A...

Страница 7: ...feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch...

Страница 8: ...ANCE TODDLERS YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS A PHYSICALBARRIERSISRECOMMEND ED IFTHERE ARE AT RISK INDIVIDUAL INTHE HOUSE TO RESTRICT ACCESS TO A FIREPLACE OR...

Страница 9: ...imately 4 seconds the spark ignition system will spark for 60 seconds to light the main burner 4 The unit will turn on LIGHTING PROCEDURE Continuous Pilot Intermittent Pilot CPI IPI selection See remo...

Страница 10: ...que de d clencher un incendie ou une explosion pouvant entra ner des d g ts mat riels ou des blessures pouvant tre mortelles Tout d faut d installation d ajustement de modification de service ou d ent...

Страница 11: ...e 1 Proflame Transmitter Figure 2 Transmitter LCD Display TECHNICAL DATA REMOTE CONTROL Supply Voltage 4 5V three 1 5V AAA batteries Ambient temperature ratings 0 50o C 32 122o F Radio Frequency 315 M...

Страница 12: ...e the flame height by one step until the flame is turned off The Up Arrow Key will increase the flame height each time it is pressed If the Up Arrow Key is pressed while the system is on but the flame...

Страница 13: ...he Proflame system The fan speed can be adjustedthroughsix 6 speeds ToactivatethisfunctionusetheModeKey fig 1 to index to the fan control icon Fig 13 Use the Up Down Arrow Keys fig 1 to turn on off or...

Страница 14: ...stem IPI to a continuous pilot ignition system CPI by using remote control as noted above The benefits of having as CPI are as follows Keeps venting primed for trouble free start up under colder weath...

Страница 15: ...PilotAdjustment section 6 Install 4 AA batteries into battery box This will enable operation of appliance manually when in ON position 7 Test gas pressure Refer to Gas Pipe Pressure Testing section 8...

Страница 16: ...ing Instructions This appliance is equipped with a three pronged grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong recep tacle...

Страница 17: ...Preferable if the thermostat is installed on an interior wall Regency offers an optional programmable thermostat but any 250 750 millivolt rated non anticipator type thermostat that is CSA ULC or UL...

Страница 18: ...ws on top Loosen 4 screws on bottom slide access panel to the right to remove Diagram 2 Loosen 6 screws slide access panel to the front of unit to remove Leg unit Loosen 6 screws on bottom access pane...

Страница 19: ...p located on the underside of the fan 11 Once the ground wire has been attached to the blower route the ground wire back to the IFC board and attach to Ground Lug located on the left front of the unit...

Страница 20: ...pletely installed connect the receiver to the wire harness and re assemble Valve cover plate by re installing the 2 Philip head screws 14 Next reinstall the door cover plate by re installing 4 Philip...

Страница 21: ...pedestal cover plate Anchoring Brackets Hold Down Package Part 846 585 LEG AND BOTTOM SHIELD ASSEMBLY These instructions apply to the nickel leg and painted cast leg It will be easier to attach the le...

Страница 22: ...t Direct Vent venting sys tems in combination with the Classic Direct Vent Freestanding Gas Stove C34E NG11 and C34E LP11 have been tested and listed as direct vent heater systems by Intertek If conve...

Страница 23: ...ine extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any...

Страница 24: ...ble Length 7 Galvanized N A N A 4D7A N A N A N A N A Adjustable Length 7 Black N A N A 4D7AB N A N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 08A N A N A N A N A N A N A Extension Pipe 8 1 2 Blac...

Страница 25: ...K2 4DHTKA SV SHK TM4 HTK VDV KW04 Horizontal Termination Kit B N A 4DT HKB 4DHTK1 4DHTKB SV HK TM4 HTK VDV K04 Vertical Termination Kit N A 4DT VKC 4DHTK 4DHTK SV FK N A N A FPI 946 506 P Vent Guard O...

Страница 26: ...ng and Security Secure Vent systems WARNING Do not combine venting components from different venting systems However use of the the AstroCapTM and FPI Riser is acceptable with all systems When using R...

Страница 27: ...n with the factory set vent restrictor position of C Example B Offset to Vertical Vent A 15 ft vertical run with 4 ft horizontal offset distance falls within the shaded area and is an allowable instal...

Страница 28: ...ntal Please note minimum 1 foot between 90o elbows is required Vent restrictor position C fully open refer to Vent Restrictor Position section Lengths do not include elbow indicated Option V H V V1 A...

Страница 29: ...tuted for any other manufacturer s products Review the following sequence of instructions which are typical of most installations The se quence may vary depending on wall thickness See Locating Your G...

Страница 30: ...bead of non hardening mastic should be run around both the termination and vinyl siding standoff to prevent water from entering and to make a tight seal between the cap and the standoff 7 Stretch the...

Страница 31: ...rom the unit flue outlet to the ceiling the ceiling thickness the vertical rise in an attic or second storey and allow for sufficient vertical height above the roof line For multi storey applications...

Страница 32: ...entry slots on the male ends Diagram 1 Push the pipe sections completely together then twist lock one section clockwise approximately one quarter turn until the two sections are fully locked The femal...

Страница 33: ...two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe Use the two sheet metal screws provided to connect the strips to the pipe section Bend any remaining p...

Страница 34: ...re that all pipe and elbow connections are in their fully twist lock position 5 Ensureventisverticalandsecureflashingto the roof with roofing nails Slide the storm collar over the pipe section and sea...

Страница 35: ...ash dumps shall be secured in place and sealed before installing a Direct Vent system within the chimney If the appliance shuts off during operation contact a qualified service person to determine if...

Страница 36: ...2 psig 3 45 kPa Disconnect piping from valve at pressures over 1 2 psig 14 w c The manifold pressure is controlled by a regulator built into the gas control and should be checked at the pressure test...

Страница 37: ...DO NOT TRY TO TURN DOOR HANDLE IT IS NOT DESIGNED TO BE MOVED 3 Ensure that the front and rear deflectors are installed 4 Remove the logs from the box and carefully unwrap them The logs are fragile ha...

Страница 38: ...ng the handle through the hole on the left upper corner Diagram 4 Position the handle in the 8 O clock positions then tighten with 14mm 9 16 wrench Diagram 2 2 Unscrew and turn the door retaining clip...

Страница 39: ...AERATION ADJUSTMENT Natural Gas 5 16 Propane 5 8 This adjustment is performed by the installer and is primarily used in installations at high elevations Push in for a yellow flame or pull out for a b...

Страница 40: ...oard will start second try for ignition by sparking for approximately 60 seconds If there is still no positive ignition the board will go into lock out The system will need to be reset as follows a Tu...

Страница 41: ...risque de d clencher un incendie ou une explosion pouvant entra ner des d g ts mat riels ou des blessures pouvant tre mortelles Tout d faut d installation d ajustement de modification de service ou d...

Страница 42: ...VOIDBURNSORCLOTH ING IGNITION YOUNG CHILDREN SHOULD BE CAREFULLY SUPER VISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLIANCE 8 Each time the appliance is lit it may cause condensation and fog the glas...

Страница 43: ...s panel s should be done by a licensed or qualified service person GLASS REPLACEMENT In the event that you break your glass by impact purchase your replacement from an authorized Regency dealer only R...

Страница 44: ...sitioned 7 The unit should never be turned off and on again without a minimum of a 60 second wait This remote control requires coding See remote coding instructions for details NOTE Thisappliancewillo...

Страница 45: ...llips head screws 1 Open up front access door Remove 2 Phillips head screws to remove cover plate Place screws to the side See diagram 1 Diagram 2 Battery compartment door Battery compartment tabs 2 P...

Страница 46: ...qualified field service person to ensure that the flow of combustion and ventilation air is not obstructed During the annual service call the burners should be removed from the burner tray and cleane...

Страница 47: ...edestal model Diagram 1 b Panel from bottom of leg shield Diagram 2 Diagram 2 Diagram 1 Access Panel Cover Plate Valve Cover Plate Note Access panel has to be loosened only to be taken out Slide left...

Страница 48: ...oving one 1 Phillips head screw With the rear log deflector removed this will allow you to remove the left and right log stand Remove two 2 Phillips head screws on each log stand to remove 11 With bot...

Страница 49: ...head valve mounting screws from inside of firebox 15 Drop valve assembly down and through Cover plate opening 16 Disconnect the stepper motor from the IFC board located at X6 on the IFC board 17 Once...

Страница 50: ...wrench Diagram 2 Once the supply tube has been removed from the 90 degree brass fitting remove the 90 degree brass fitting from the valve with a 17mm 11 16 wrench Diagram 3 Lastly remove supply tube f...

Страница 51: ...494 926 Pedestal 12 936 233 Door Gasket 14 Screw 10 24 x 3 4 17 471 031 Door Retainer Clip 19 948 146 Wooden Handle 20 494 917 Complete Fan Assembly Optional 910 157 P Blower Motor 120V 22 910 813 Po...

Страница 52: ...lot Orifice NG 910 037 Pilot Orifice LP 911 039 Pilot Hood 910 432 Pilot Tube w nuts 911 173 Valve Remote Wiring Harness 911 282 Battery Box Wiring Harness 911 257 2 Pin Fan Wiring Harness 911 193 Con...

Страница 53: ...Hinge 110 910 327 Strain Relief for Power Cord 121 490 005 Access Panel 140 850 126 Cast Legs Black 4 set 850 128 Cast Legs Brush Nickel 4 set 494 926 Pedestal Assembly 100 948 223 Regency Logo 102 90...

Страница 54: ...tion Control Boards Wiring Switches Blowers Blower Control Module Battery Pack Remote Control Systems 2 Enamel Panels 1 Venting Venting Components 1 All Stainless steel surrounds 1 All Firebox Media C...

Страница 55: ...downdrafts installation error installation by an unqualified installer incorrect chimney components including but not limited to cap size or type operator error abuse misuse use of improper fuels lac...

Страница 56: ...utside the U S should consult their local provincial or national legal codes for additional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the a...

Страница 57: ...n below in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Pr...

Страница 58: ...58 Regency CLASSIC C34E 11 Direct Vent Freestanding Gas Stove warranty...

Страница 59: ...Regency CLASSIC C34E 11 Direct Vent Freestanding Gas Stove 59...

Страница 60: ...Dealer Name Address _______________________________________________ ___________________________________________________________________ Installer ______________________________________________________...

Отзывы: