 CLASSIC™ C34-11 Direct Vent Freestanding Gas Stove

  |     7

 

 

|

 

7

requirements

5.08: 

Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements: 

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for 

residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than 

seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall 

be satisfied:  

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled 

equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is 

installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery 

operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure 

served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of 

qualified licensed professionals for the installation of hard wired carbon monoxide detectors 

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon 

monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. 

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of 

thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon 

monoxide detector with an alarm shall be installed. 

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions 

shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.  

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 

(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The 

sign shall read, in print size no less than one-half (1/2) inch in size, 

"GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL 

OBSTRUCTIONS". 

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation 

unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 

5.08(2)(a)1 through 4.  

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  

1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by 

the Board; and  

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or 

structure used in whole or in part for residential purposes.  

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the 

instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 

1. Detailed instructions for the installation of the venting system design or the venting system components; and 

2. A complete parts list for the venting system design or venting system.  

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a 

Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies 

"special venting systems", the following requirements shall be satisfied by the manufacturer: 

1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and  

2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

detailed installation instructions.  

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, 

all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of 

the installation.  

MA Code - CO Detector

(for the State of Massachusetts only)

Содержание C34 Classic

Страница 1: ...s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the...

Страница 2: ...ause 5 14 4 the following graphic danger and statements shall be shown on a Class IIIA 2 Permanent Label 4 34 6 Instruction Plate Each appliance shall bear a Class IIIB marking with letters on a contr...

Страница 3: ...33 2017 This Direct Vent System Appliance must be installed in accordance with the manufacturer s installation instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part...

Страница 4: ...ency CLASSIC C34 11 Direct Vent Freestanding Gas Stove 4 dimensions ALL PICTURES DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCE...

Страница 5: ...rrangements 27 DV Stove Horizontal Vent Kit 29 DV Stove Horizontal Vent Kit Installation 29 Dura Vent Termination Kit 31 Dura Vent Horizontal Installations 32 Vertical Termination 33 Cathedral Ceiling...

Страница 6: ...aller l appareil selon la norme CAN CSA Z240 S rie MM Maison mobiles ou CAN CSA Z240 VC V hicules de camping ou la norme 24 CFR Part 3280 Manufactured Home Construction and Safety Standard Si ces norm...

Страница 7: ...rade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS...

Страница 8: ...the unit converted to top or rear vent per manual instructions and the insulation discarded Venting YES NO Are the venting components approved for the unit installed Does the venting configuration com...

Страница 9: ...l Was the air shutter on the proper setting after running the unit for 20 minutes If applicable were the surround and trims installed according to the manual Was the operation of the fan lights if ins...

Страница 10: ...DREN SHOULD BE CARE FULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA AS THE APPLI ANCE TODDLERS YOUNGCHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS A PHYSICAL BARRIERS IS RECOM MEND...

Страница 11: ...6 Never vent to another room or inside a build ing Make sure that the vent is fitted as per the instructions starting in Venting Introduction section 7 Inspect the venting system annually for block a...

Страница 12: ...e manually when in ON position Note If optional fan is not purchased Batter ies are required in both remote receiver 4 x AA Batteries remote hand held 3 x AAA batteries in order to operate appliance u...

Страница 13: ...ast approximately 60 seconds If there is no flame ignition rectification the board will stop sparking for ap proximately 35 seconds After wait time the board will start second try for ignition by spar...

Страница 14: ...MOTE CONTROL Supply Voltage 4 5V three 1 5V AAA batteries Ambient temperature ratings 0 50o C 32 122o F Radio Frequency 315 MHZ ATTENTION Turn OFF the main gas supply of the appliance during installat...

Страница 15: ...flame height by one step until the flame is turned off The Up Arrow Key will increase the flame height each time it is pressed If the Up Arrow Key is pressed while the system is on but the flame is of...

Страница 16: ...hot air circulating fan the speed of the fan can be controlled by the Proflame system The fan speed can be adjustedthroughsix 6 speeds ToactivatethisfunctionusetheModeKey fig 1 to index to the fan con...

Страница 17: ...ing primed for trouble free start up under colder weather conditions or inversions Keeps the unit glass warm which decreases the amount of condensation on start up Provides owners with flexibility to...

Страница 18: ...and insert the battery compartment back into remote receiver battery holder Move both the left right slides as shown below The battery compartment will be pushed out slightly to allow to easily extrac...

Страница 19: ...e Leg unit Loosen 7 screws on bottom access panel slide panel toward the front to remove IMPORTANT Disconnect power supply before servicing Pedestal unit To install the fan in an installed stove acces...

Страница 20: ...grounding lug 9 Remove fan from stove Diagram 3 IMPORTANT THESE FANS COLLECT A LOT OF DUST FROMWITHINYOUR HOME ENSUREYOU MAINTAINTHESE FAN MOTORS ON A REGULAR BASIS BYVACUUMINGTHE FAN BLADES ANDTHE HO...

Страница 21: ...pedestal cover plate Anchoring Brackets Hold Down Package Part 846 585 LEG AND BOTTOM SHIELD ASSEMBLY These instructions apply to the steel leg and painted cast leg It will be easier to attach the le...

Страница 22: ...ng systems in combination with the Classic Direct Vent Free standing Gas Stove C34 NG11 and C34 LP11 have been tested and listed as direct vent heater systems by Intertek IfconvertingaClass AMetalChim...

Страница 23: ...line extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to an...

Страница 24: ...3 10 Black N A N A N A 4DALB N A TC 4DLTB N A Adjustable Length 7 Galvanized N A N A 4D7A N A N A N A N A Adjustable Length 7 Black N A N A 4D7AB N A N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA...

Страница 25: ...AstroCap 946 205 Vinyl Siding Shield for Riser Vent Terminal 510 994 Rigid Pipe Adaptor Must use with all rigid piping 946 208 P Vent Guard Optional for Riser Vent Terminal 640 530 P Riser Vent Termin...

Страница 26: ...nting and Security Secure Vent systems WARNING Do not combine venting components from different venting systems However use of the AstroCapTM and FPI Riser is acceptable with all systems When using Ri...

Страница 27: ...llation with the factory set vent restrictor position of C Example B Offset to Vertical Vent A 15 ft vertical run with 4 ft horizontal offset distance falls within the shaded area and is an allowable...

Страница 28: ...of 6 feet total vertical and max 8 feet total horizontal Please note min 1 foot between 90o elbows is required Vent restrictor position C fully open refer to Vent Restrictor Position section Lengths d...

Страница 29: ...be substituted for any other manufacturer s products Review the following sequence of instructions which are typical of most installations The se quence may vary depending on wall thickness See Locati...

Страница 30: ...ings 6 A bead of non hardening mastic should be run around both the termination and vinyl siding standoff to prevent water from entering and to make a tight seal between the cap and the standoff 7 Str...

Страница 31: ...distance from the unit flue outlet to the ceiling the ceiling thickness the vertical rise in an attic or second storey and allow for sufficient vertical height above the roof line For multi storey app...

Страница 32: ...entry slots on the male ends Diagram 1 Push the pipe sections completely together then twist lock one section clockwise approximately one quarter turn until the two sections are fully locked The fema...

Страница 33: ...vent cap assembly into the outer wall of the vent pipe Use the two sheet metal screws provided to connect the strips to the pipe section Bend any remaining portion of the sheet metal strip back towar...

Страница 34: ...that all pipe and elbow connections are in their fully twist lock position 5 Ensure vent is vertical and secure flashing to the roof with roofing nails Slide the storm collar over the pipe section an...

Страница 35: ...beconnected to a damaged Class A chimney For Class A chimneys clean out doors and caps or plugs for clean out tee fittings and ash dumps shall be secured in place and sealed before installing a Direct...

Страница 36: ...ual shutoff valve mustbedisconnectedfromthepiping system If test pressures equal to or less than 1 2 psig are used then this appliance must be isolated from the pipingsystembyclosingitsindividual manu...

Страница 37: ...6 Inlet Pressure Tap 7 Pilot Outlet 8 Main Gas Outlet 9 Alternative TC Connection Point 1 Open door on pedestal or heat shield with legs base Remove two 2 screws in locations shown below to remove acc...

Страница 38: ...ing the handle through the hole on the left upper corner Diagram 4 Position the handle in the 8 O clock positions then tighten with 14mm 9 16 wrench Diagram 2 2 Unscrew and turn the door retaining cli...

Страница 39: ...hook the tabs on the safety into the slotted brackets on either side of the door Diagram 7 6 Once the door has been placed on the hinge pins secure the door to the unit by screwing the retaining clip...

Страница 40: ...h the pilot and burner operation The gas log kit contains the following a Front Log b Rear Log c Small Cross Logs 2 d Bag of embers e Bag of rockwool f Bag of platinum embers Embaglow supplied with pa...

Страница 41: ...leifthethermostatisinstalled on an interior wall Regency offers an optional programmable thermostat but any 250 750 millivolt rated non anticipator type thermostat that is CSA ULC or UL approved may b...

Страница 42: ...Ensure that the wires do not touch a hot surface and are away from sharp edges WARNING Electrical Grounding Instructions This appliance is equipped with a three pronged ground ing plug for your protec...

Страница 43: ...the burner Note If you have an incorrect flame pattern contact your Regency dealer for further instructions Top View of pilot flame Top View of pilot flame AERATION ADJUSTMENT Natural Gas 5 16 Propan...

Страница 44: ...ivertowiremarked receiver which will be located on the bottom of the appli ance This remote control requires coding See remote control instructions for details NOTE This appliance will operate during...

Страница 45: ...installation adjustment alteration service or maintenance can cause injury or property damage Refer to the owner s information manual provided with this appliance For assistance or additional informa...

Страница 46: ...ack 6309 3 The glass should be cleaned with a gas fireplace glass cleaner when it starts to turn milky 4 Make a periodic check of burner for proper posi tion and condition Visually check the flame of...

Страница 47: ...Remove thermocouple with a 9 mm metric wrench 15 Remove pilot nut with an 11 mm wrench 16 Remove valve to orifice nut with a 13 16 wrench 17 Remove inlet pipe with pipe wrench Note orientation of 90o...

Страница 48: ...s in the list should be checked by a licensed gas service technician during the annual service check Your unit may require more frequent maintenance checks if you notice any changes in how it operates...

Страница 49: ...4 Screw 10 24 x 3 4 17 471 031 Door Retainer Clip 19 948 146 Wood Handle 20 493 917 Complete Fan Assembly Optional 910 157 P Blower Motor 120V 21 910 142 Fan Auto on off Thermodisc 22 910 813 Power Co...

Страница 50: ...0 592 Remote hand held GTMF Silver 911 175 P Remote hand held GTMF Black 910 036 Pilot Orifice NG 910 037 Pilot Orifice LP 68 910 096 Pilot Hood 82 910 341 Thermopile 83 910 386 Thermocouple 910 432 P...

Страница 51: ...Hinge 110 910 327 Strain Relief for Power Cord 121 490 005 Access Panel 140 850 126 Cast Legs Black 4 set 850 128 Cast Legs Brush Nickel 4 set 494 926 Pedestal Assembly 100 948 223 Regency Logo 102 9...

Страница 52: ...ition Control Boards Wiring Switches Blowers Blower Control Module Battery Pack Remote Control Systems 2 Enamel Panels 1 Venting Venting Components 1 All Stainless steel surrounds 1 All Firebox Media...

Страница 53: ...s downdrafts installation error installation by an unqualified installer incorrect chimney components including but not limited to cap size or type operator error abuse misuse use of improper fuels la...

Страница 54: ...outside the U S should consult their local provincial or national legal codes for additional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the...

Страница 55: ...elow in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Produ...

Страница 56: ......

Страница 57: ...Regency CLASSIC C34 11 Direct Vent Freestanding Gas Stove 57 57 notes...

Страница 58: ...58 Regency CLASSIC C34 11 Direct Vent Freestanding Gas Stove 58 notes...

Страница 59: ......

Страница 60: ...e following information Dealer Name Address ________________________________________ ___________________________________________________________ Installer _____________________________________________...

Отзывы: