Instruction Manual TAP, TAP-CLAMP / Temperature And Pressure Gauge English
7
Pressure gauge
Property Value
Maximum working
pressure:
60 bar
/ 870 psi / 6000 kPa / 6 MPa
Pressure resolution:
0.07 bar
/ 0.1 psi / 7 kPa / 0.007 MPa
Pressure units:
bar
/ psi / kPa / MPa
Positive pressure
display:
0.95 to 60 bar,
up to 870 psi, up to 6000 kPa, up to 6 MPa
Accuracy:
1.0% FS
Power supply:
4 x 1.5 V AAA / batteries
Service life of approx. 35 hours when used continuously.
Battery life varies with the brand or age of battery.
Storage temperature:
- 20 °C to + 60 °C /
-4 °F to 140 °F
Backlit LCD display:
40 mm x 30 mm
Automatic power save
mode:
Settable 10 min / 20 min / Off
Interface: Micro
USB
Connection fitting:
¼" SAE
Size:
125 mm x 57 mm x 34 mm
Weight: 200
gr
/ 7.0 oz
The TAP can be used with the following refrigerants:
R11, R113, R114, R12, R123, R124, R13, R134a, R13B1, R22, R227, R23, R290, R32
R401A(Liq), R401A(Vap), R401B(Liq), R401B(Vap), R402A(Liq), R402A(Vap),
R402B(Liq), R402B(Vap), R403B(Liq), R403B(Vap), R404A, R406A (Liq), R406A(Vap),
R407A(Liq), R407A(Vap), R407B, R407C(Liq), R407C(Vap), R407F(Liq), R407F(Vap),
R408A(Liq), R408A(Vap), R409A(Liq), R409A(Vap), R410A, R413A(Liq), R413A(Vap),
R414B(Liq), R414B(Vap), R416A(Liq), R416A(Vap), R417A(Liq), R417A(Vap), R420A,
R422A(Liq), R422A(Vap), R422B(Liq), R422B(Vap), R422C(Liq), R422C(Vap),
R422D(Liq), R422D(Vap), R427A(Liq), R427A(Vap), R437A, R438A(Liq), R438A(Vap),
R448A(Liq), R448A(Vap), R449A(Liq), R449A(Vap), R450A(Liq), R450A(Vap),
R452A(Liq), R452A(Vap), R500, R502, R503, R507, R508A, R508B, R513A, R600a,
R744, R1233zd, R1234yf, R1234ze
(Liq) = liquid / bubble point, (Vap) = vapour / dew point
Содержание 4687785
Страница 29: ......