English Instruction Manual TAP / Temperature And Pressure Gauge
22
SD Mode
This function is used in combination for update.
See in chapter maintenance.
P-Zero
Resetting pressure sensor.
See in chapter maintenance / Resetting pressure sensor
Maintenance
A visual inspection of the connections and hoses must be carried out before
each use to check for mechanical damage.
Do not use aggressive cleaning agents or solvents to clean the device. Gentle
household cleaners and soapy water should be used instead.
TAP seals are subject to mechanical and age-related wear. Therefore, the TAP
should be regularly tested by the user for leaks.
Resetting pressure sensore on TAP pressure gauge
The TAP pressure sensor can be reset in order to avoid incorrect measurement values.
P-Zero
To obtain a correct measurement value on the display, the TAP should not
be reset when pressurised.
1. Ensure TAP pressure gauge is switched on.
2. Press [MENU] button
1 sec. to activate selection mode.
3. Press [UP] button
1 sec. to scroll up to the setting field
.
4. Press [SET] button
1 sec. to enter settings menu.
5. Press [UP] or [DOWN] button
1 sec. to scroll to the "P-Zero" field.
6. Enter "P-Zero" by pressing [SET] button
1 sec.
7. Display shows 0.0psi
8. Press [SET] button
1 sec. for confirmation.
9. Display shows setting menu.
10. Press [MENU] button
1 sec. to quit.