11 - SAFETY DEVICES AND ALARMS
Technical Dept. - All rights reserved - Reproduction is prohibited
To reset the alarm, press and hold key 1 (ESC) for a few seconds. The boiler checks whether the cause of the alarm is ongoing.
In the first case, the alarm continues to be displayed, in the second case it turns OFF.
If the alarm persists, contact a service centre.
NORMAL SHUTDOWN (on the panel: OFF with flashing flame symbol)
When the shutdown key is pressed, or when there is an alarm signal, the boiler enters the thermal extinguishing phase which involves
automatic execution of the following phases:
• Stop pellet loading
• The smoke extractor fan is is activated at maximum speed and remains on for a fixed period of 10 minutes, at the end of which if
the smoke T has dropped below the stop threshold, the fan stops, otherwise it will continue to operate at minimum speed until the
temperature drops below the threshold.
• If the boiler has been shutdown regularly but, due to thermal inertia, the smoke temperature exceeds the threshold again, the
shutdown phase will be repeated at minimum speed until the temperature falls.
BLACKOUT with boiler ON
In the event of a blackout, the boiler does the following:
• Blackout of less than 10": continues the work in progress;
• After a loss of power of more than 10'' which occurred when the boiler was on, or during ignition, you can restore the boiler to its
previous operating condition when power returns as follows:
1. Cool the boiler by activating the smoke extractor at minimum speed for 10' then proceed to the next step;
2. Restore the boiler to the operating condition prior to the blackout.
During phase 1, the panel shows ON BLACK OUT.
During phase 2, the panel shows Start-up.
If during phase 1 the system receives manual user commands from the control panel, it stops the blackout restoration sequence and
begins the start-up or shutdown commanded by the user.
BLACKOUT OF MORE THAN 10'' DURING EXTINCTION OF BOILER
If the boiler experiences a loss of power greater than 10'' while it is shutting down, when power is restored to the boiler, it will automatically
turn on in shutdown mode, even if the smoke temperature has fallen below 45°C in the meantime. This phase can be skipped by pressing
key 1 (esc) (skips to start-up) and pressing it again (recognises that the boiler is off).