Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104
23
14.07.2020
5.9 Parameter list
Pa
ram
et
er
Co
de
Text in display, line 1
Meaning
Factory
setting
Setting range
See p
age
B0
—
B0 Disp.language
Language of the display text
0
0 … 2 25
Parameter block C0-C3 "Service operating hours counter"
C0 5
C0 Ser.ope.hours
Service operating hours counter
0
1
0
1
… 2 25
C1 –
C1 Counter mode
Operating hours counter mode
3
0 … 3 25
C2 4
C2 Service alarm
Service alarm
3000 h 0
1
… 25.500 h 25
C3 4
C3 Serv.al.reset
Service alarm reset
–
– 25
Parameter block D0-D8 “
Δ
p
-controls“
D0 3
D0 DP-controls
Δ
p
controls
1
0
1
, 1 26
D1 –
D1 Cleaning mode
Δ
p
cleaning mode
2
0 … 4 26
D2 –
D2 Sensor source
Sensor source
2
0 … 3 26
D3 –
D3 Sensor alarm
Sensor alarm
0
0 … 1 26
D4 –
D4 DP-unit
Δ
p
unit in display
inch/Wc
D5 –
D5 DP-start
Δ
p
start
1000 Pa
2
100 … 4800 Pa
3
D6 –
D6 DP-hyster.
Δ
p
hysteresis
300 Pa
4
100 … 4700 Pa
5
D7 –
D7 DP-min alarm
Δ
p
min. alarm
0
1
Pa 0
1
… 4600 Pa
6
D8 –
D8 DP-max alarm
Δ
p
max. alarm
2000 Pa
7
0
1
… 5000 Pa
8
D9 –
D9 DP pre-alarm
Δ
p
-pre-Alarm max.
0
1
Pa 0
1
… 5000 Pa
8
1
0 = Function inactive
2
The value 1000 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another
Δ
p
range is selected, the
Δ
p
starting
value is 20% of the full scale value.
3
The setting range 100 Pa … 4800 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another
Δ
p
range is se-
lected, the setting range is 2% ... 96% of the full scale value.
4
The value 300 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another
Δ
p
range is selected, the
Δ
p
hystere-
sis value is 6% of the full scale value.
5
The setting range 100 Pa … 4700 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another
Δ
p
range is se-
lected, the setting range is 2% ... 94% of the full scale value.
6
The setting range 0 … 4600 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another
Δ
p
range is selected,
the setting range is 0 ... 92% of the full scale value.
7
The value 2000 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another
Δ
p
range is selected, the
Δ
p
max.
alarm value is 40% of the full scale value.
8
The setting range 0 … 5000 Pa applies to the default setting of parameter T1 = 0 … 5000 Pa. If another
Δ
p
range is selected,
the setting range is 0 ... 100% of the full scale value.
Parameter code 3 = 4711
Parameter code 4 = known only to the manufacturer of the filter system
Parameter code 5 = known only to the manufacturer of the filter system