Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104
24
14.07.2020
Pa
ram
et
er
Co
de
Text in display, line 1
Meaning
Factory
setting
Setting range
See p
age
Parameter block E0-EC “Cleaning control functions”
E0 3
E0 Clean control
Cleaning control functions
1
0
1
… 2 28
E1 –
E1 Interval 1
Interval 1
10 s
0.5 … 250 s 28
E2 –
E2 Interval Mode
Interval mode
9
0
1
0
1
… 1 28
E3 –
E3 Interval 2
Interval 2
6 s
0.5 … 250 s 28
E5 –
E5 pulse clean A
Pulse time “Cleaning valve”
80 ms
40 … 990 ms 28
E6 –
E6 Pulsemode A
Pulse mode "Cleaning valve"
0
1
0
1
… 1 28
E8 –
E8 Forced cl. T
Compulsory cleaning time
0
1
0
1
… 2500 min 28
E9 –
E9 Downtime cyc.
Downtime cycles
0
1
0
1
… 64 28
►
EA 3
EA Valve no.
Number of valves at parameter set-
ting E0 = 1
16
1 … 240 28
►
EB 3
EB Number RM-VXX
Number of I/O modules RM-V 6/X
10
,
RM-V 8
11
or RM-V 16
11
with
parameter setting E0 = 1
1
1 … 15 28
EC 3
EC Skip range
Cleaning skip range
1
1 … EA/2
12
1
0 = Function inactive
9
is not active with active impulse controller
10
only types RM-310 C Plug and Play and RM-310 CT Plug and Play
11
only types RM-310 C and RM-310 CT
12
EA/2 = Set value of the EA parameter divided by 2
►
Parameters must definitely be set before commissioning.
Parameter code 3 = 4711