Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104
12
14.07.2020
Relay outputs A1 ... A4 connection, potential-free
Output
Factory-set function
A1
The relay contact closes as soon as the supply
voltage is applied to RM-310 C / RM-310 CT. It
opens any time an alarm is present (Group
Alarm).
A2
Contact closes when cleaning and downtime are
active.
A3
Contact closes at
Δ
p
-Min. Alarm
A4
Contact closes at Δ
p
-Max. Alarm
The function of the outputs can be individually set via parameter group G0-G8. See appendix 7
"Input and output signal parametrisation, special parameter".
Shielded cables must be used for all bus and analogue signal lines! The shielding is to be ap-
plied one-sided and as short as possible.
Signal cables are not allowed to be installed parallel to power cables.
All cable glands must be firmly tightened to make sure the cables are solidly enclosed and no
water can enter.
Unused cable glands must be closed and replaced with blind plugs.