Fault
Possible causes
Recommended action
On the display, the message
„
RM-VXX alarm setting
"
appears.
The valve setting of the I/O mod-
ules RM-V6/X or RM-V8 / RM-
V16 does not agree with the set-
ting of the RM-310 C /
RM-310 CT.
Check the EA parameter setting
and correct if necessary
On the display, the message
„
Sensor alarm
" appears.
Δ
p
sensor DP-1 defective
Check the Δp sensors and r
eplace
if necessary
Δp measuring lead connected i
n-
correctly or defective
-
Check connec
tions of the Δp
measuring leads and replace
if necessary
-
Check Δ
p
measuring leads
and replace if necessary
On the display, the message
„
Input lx alarm
" appears.
The input current of the analogue
input is too low.
Check analogue line for polarity
and electrical connection.