background image

18

REC Installation Manual - REC Solar Panels  - IEC 

61215

 /

61730

Rev L 

-

 

09

.

21

 

Ref:  PM

-

IM

-20

DRAINAGE HOLES

On the long and short sides of the REC frame small drainage holes can be found that allow humidity and water to exit the frame easily and minimize 

damage (fig. 

16

). These are spaced 

55

 mm from the corner on 

60

-cell format panels and 

60

 mm on 

72

-cell format panels. These holes must not be 

used for mounting the panel, and they must not be covered by any part of the mounting structure.

 

To enable e

ff

ective drainage and ensure there is 

no damage to the panel, the drainage holes must remain fully open and enable water egress during and a

ft

er installation. The shape and dimensions 

of the drainage holes may vary depending on product and/or frame design.

GROUNDING

Local regulations may require grounding of the panels. Grounding must be done using an electrical connection from the panel frame. REC solar 

panels have a small round grounding hole positioned near each corner of the panel on both the long side and the short side, 

as shown in fig. 

16

 and 

can be further

 identified by the grounding symbol stamped in the frame next to it. Check all applicable requirements before beginning installation:

•  Suitable grounding clips, lugs or other constructions must be used,
•  A

tt

ach grounds to the grounding holes in the panel frames,

•  Follow the grounding device manufacturer’s installation instructions to ensure a safe and conductive connection, including any 

supplementary hardware, e.g., star washer, and tighten according to recommended torque,

•  Where common grounding hardware (nuts, bolts, star washers, split-ring lock washers, flat washers and the like) are used to a

tt

ach a grounding 

device, the a

tt

achment must be made in conformance with the grounding device manufacturer’s instructions.

Fig. 

16

: Drainage and grounding holes

25.6- 0 [650 - 0 mm]

GR

GR

GR

GR

0-25.6 in [0 - 650 mm]

9.8 - 4 in

[250 - 100 mm]

4 - 9.8 in

[100 - 250 mm]

9.8 - 4 in

[250 - 100 mm]

4 - 9.8 in

[100 - 250 mm]

25.6- 0 [650 - 0 mm]

0-25.6 in [0 - 650 mm]

NOTE

•  To avoid galvanic corrosion, galvanized or hot dipped zinc plated fasteners are preferred, however stainless steel fastening materials are 

equally suitable.

•  The support bars across the rear of REC panels are connected to the frame via specially designed grounding clips and do not need to be 

individually grounded. 

•  Negative grounding of the panels is not required by REC.

i

Grounding holes

Drainage holes

Содержание N-Peak 2 Black Series

Страница 1: ...ll REC solar panels certified according to IEC 61215 61730 RECTwinPeak 4 Series RECTwinPeak 4 Black Series REC N Peak Series REC N Peak Black Series REC N Peak 2 Series REC N Peak 2 Black Series REC S...

Страница 2: ...ll panels MLPE device installation zones 28 INTRODUCTION 3 SAFETY MEASURES 4 PANEL HANDLING 5 CHOOSING AN INSTALLATION LOCATION 5 ELECTRICAL INSTALLATION 6 MECHANICAL INSTALLATION 6 PANEL INSTALLATION...

Страница 3: ...lers are responsible for the following Only qualified personnel must perform work on photovoltaic systems such as installation commissioning maintenance and repairs Be sure to follow the safety instru...

Страница 4: ...served during handling to avoid the risk of sparking fire hazards burns and lethal electric shocks Exercise extreme caution when wiring panels and look out for damaged or dirty cables etc Never insert...

Страница 5: ...radationtothepackagingorpanelcomponents pallets and panels must be stored in a controlled environment ideally internal where it is protected from the elements e g rain dust and direct sunlight If over...

Страница 6: ...ion fault Correct DC polarity must be observed at all times Electrical Ratings ElectricalratingsarewithinaspecifictoleranceofmeasuredvaluesatStandardTestConditions STC asgiveninthetechnicalcharacteris...

Страница 7: ...tructions including specific hardware and torque requirements Ensure the clamps used are suitable for the planned installation and expected system design loads The grip area must not extend onto the p...

Страница 8: ...00Pa 2400Pa 3600Pa 1600Pa X 622 712 mm 2400Pa 2400Pa 1600Pa 1600Pa 2400Pa 2400Pa 1600Pa 1600Pa 2400Pa 2400Pa 1600Pa 1600Pa X 0 100 mm X 1200Pa 1200Pa 800Pa 800Pa 1600Pa 1600Pa 1066Pa 1066Pa X 100 250...

Страница 9: ...learance Gap Clamping zone 20 40 mm 40 60 mm 60 mm 20 mm Test Load DesignLoad Test Load DesignLoad Test Load DesignLoad Test Load DesignLoad 0 650 mm 1200Pa 1200Pa 800Pa 800Pa 3000Pa 2400Pa 2400Pa 160...

Страница 10: ...600Pa 1600Pa X 0 100 mm X 1200Pa 1200Pa 800Pa 800Pa 1600Pa 1600Pa 1066Pa 1066Pa X 100 250 mm X 800Pa 800Pa 533Pa 533Pa 2400Pa 2400Pa 1600Pa 1600Pa X Rail length under module 100 200 mm Min 100 mm Max...

Страница 11: ...Pa 2800Pa 1600Pa 5400Pa 2400Pa 3600Pa 1600Pa X 340 420 mm 1800Pa 1800Pa 1200Pa 1200Pa 6200Pa 4000Pa 4133Pa 2666Pa 7000Pa 4000Pa 4666Pa 2666Pa X 420 520 mm 1200Pa 1200Pa 800Pa 800Pa 3000Pa 2400Pa 2400P...

Страница 12: ...m 4 in 250 mm 9 8 in 250 mm 9 8 in 100 mm 4 in 100 mm 4 in 650 mm 25 6 in 0 0 0 0 0 0 650 mm 25 6 in Rail position Rail position Legend Clearance Gap Clamping zone 20 40 mm 40 60 mm 60 mm 20 mm Test L...

Страница 13: ...Pa 1600Pa X 0 100 mm X 1200Pa 1200Pa 800Pa 800Pa 1600Pa 1600Pa 1066Pa 1066Pa X 100 250 mm X 800Pa 800Pa 533Pa 533Pa 2400Pa 2400Pa 1600Pa 1600Pa X Rail length under module 100 200 mm Min 100 mm Max 200...

Страница 14: ...0Pa 1600Pa X 225 357 mm 1800Pa 1800Pa 1200Pa 1200Pa 4200Pa 2400Pa 2800Pa 1600Pa 5400Pa 2400Pa 3600Pa 1600Pa X 357 582 mm 1800Pa 1800Pa 1200Pa 1200Pa 6200Pa 4000Pa 4133Pa 2666Pa 7000Pa 4000Pa 4666Pa 26...

Страница 15: ...ELS WITH CONTINOUS RAILS PARALLEL TO LONG SIDE OF THE PANEL A continous rail or other support structure spans the complete underside of the panel Legend Clearance Gap Clamping zone 20 40 mm 40 60 mm 6...

Страница 16: ...357 582 mm 1200Pa 1200Pa 800Pa 800Pa 3000Pa 3000Pa 2000Pa 2000Pa 4200Pa 4000Pa 2800Pa 2666Pa X 582 622 mm 1200Pa 1200Pa 800Pa 800Pa 2400Pa 2400Pa 1600Pa 1600Pa 3600Pa 2400Pa 2400Pa 1600Pa X 622 712 mm...

Страница 17: ...s apply a safety factor of 1 5 to the stated test load e g test load 5400 Pa 1 5 3600 Pa design load Part Name Material Rail 6105 T5 aluminum extrusion Bolt M6 x 25 drop inT stud kit Nut M6 flanged he...

Страница 18: ...d the short side as shown in fig 16 and can be further identified by the grounding symbol stamped in the frame next to it Check all applicable requirements before beginning installation Suitable groun...

Страница 19: ...lestandards e g IEC 62852orUL6703 toensuretheyarefitforpurposeandsafety Useofanychemicalsorlubricantsontheconnectorsorcontactsmayonlybecarriedoutinlinewiththeconnectormanufacturer sinstructions TheREC...

Страница 20: ...to local guidelines and regulations By ensuring REC solar panels are disposed of correctly you will help prevent potential negative impact on the environment and human health The majority of the panel...

Страница 21: ...3 34 7 35 0 NominalPowerCurrent IMPP A 10 62 10 65 10 68 10 72 OpenCircuitVoltage VOC V 40 6 40 8 41 0 41 2 ShortCircuitCurrent ISC A 11 26 11 32 11 38 11 45 PanelEfficiency 19 7 20 0 20 3 20 5 Values...

Страница 22: ...34 3 34 7 NominalPowerCurrent IMPP A 10 60 10 62 10 65 10 68 OpenCircuitVoltage VOC V 40 5 40 6 40 8 41 0 ShortCircuitCurrent ISC A 11 19 11 26 11 32 11 38 PanelEfficiency 19 4 19 7 20 0 20 3 Values...

Страница 23: ...ncy 18 3 18 6 18 9 19 2 19 5 19 8 Values at standard test conditions STC air mass AM 1 5 irradiance 1000 W m temperature 25 C based on a production spread with a toleranceofPMAX VOC ISC 3 withinonewat...

Страница 24: ...10 28 PanelEfficiency 18 3 18 6 18 9 19 2 19 5 Values at standard test conditions STC air mass AM 1 5 irradiance 1000 W m temperature 25 C based on a production spread with a toleranceofPMAX VOC ISC 3...

Страница 25: ...ominalPowerCurrent IMPP A 10 62 10 65 10 68 10 72 OpenCircuitVoltage VOC V 40 8 40 9 41 1 41 3 ShortCircuitCurrent ISC A 11 31 11 36 11 41 11 46 PanelEfficiency 19 7 20 0 20 3 20 5 Values at standard...

Страница 26: ...VMPP V 33 5 33 9 34 3 34 7 NominalPowerCurrent IMPP A 10 60 10 62 10 65 10 68 OpenCircuitVoltage VOC V 40 7 40 8 40 9 41 1 ShortCircuitCurrent ISC A 11 27 11 31 11 36 11 41 PanelEfficiency 19 4 19 7...

Страница 27: ...slack to prevent damage due to water level changes and wave motions ii Mounting panels Installation of REC solar panels must be in accordance with the aforementioned standard mounting instructions Th...

Страница 28: ...MLPE devices may also be attached to the mounting construction In such cases refer to the instructions provided by the manufacturer Wherever possible the installation of the MLPE device should not co...

Страница 29: ...he market of electrical equipment designed for use within certain voltage limits The technical documentation and full compliance with the standards listed below proves the conformity of the product wi...

Страница 30: ...08 2019 E Updated Datasheets 01 2020 F Updated Datasheets 06 2020 G Updated Installation Manual Layout removed REC Peak Energy Series inclusion of REC N Peak Series 09 2020 H Addition of REC TwinPeak...

Страница 31: ...RECSOLARPTE LTD 20TUASSOUTHAVENUE14 SINGAPORE637312 SINGAPORE Tel 6564959228 Mail post recgroup com www recgroup com...

Отзывы: