LOGIC>
MOTOR TYPE
1=Eli 250; 2=Phobos BT, 3=Igea BT
0
0-3
LOGIC>
TCA
Timer to Close Automatically. 0=OFF / 1=ON
0
0-1
LOGIC>
FAS T CLS.
Closes when sensors are cleared. 0=OFF / 1=ON
0
0-1
LOGIC>
STEP-BY-STEP
MOVEMENT
Determines how the system reacts when a START
command is received during operation
0
0-2
LOGIC>
SHADOW
Configuration of safety loop input terminal 74 or 77 when
SAFE 2 or SAFE 3 are set as 015 (SHADOW)
0
0-1
LOGIC>
SAFE 3*
Configuration of safety input terminal 76. Defaulted as
SHADOW (Safety loop)
15
0-15
LOGIC>
PRE-ALARM
Gate running output (AUX value=6) closes 3 sec. before
gate movement 0=OFF / 1=ON
0
0-1
LOGIC>
HOLD-TO-RUN
Requires continous OPEN or CLOSE command input for
gate to operate. 0=OFF / 1=ON
0
0-2
LOGIC>
IBL OPEN
Ignores START imput during the opening cycle.
0
0-1
LOGIC>
IBL TCA
Ignores the START input while counting down for
automatic closing 0=OFF / 1=ON
0
0-1
LOGIC>
IBL CLOSE
Ignorse the START input during the closing cycle. O=OFF /
1=ON
0
0-1
LOGIC>
RAM BLOW C. OP
Pushes gate against psysical stop before opening
0
0-1
LOGIC>
RAM BLOW C. CL
Pushes gate against physical stop before closing
0
0-1
OGIC>
BLOC PERSIST
Hourly push against physical stop
0
0-1
LOGIC>
PRESS SWC
Pushes gate against physical stop for .5 seconds agter
close limit has been reacted
0
0-1
LOGIC>
ICE
Continous force learning on every operation
0
0-1
36 PR
OGRAMMING MENU