APOLLO FYM - SPREADER CONTROLLER

12

3.4.1 Feedback

The  factor  (pulses  per  revolution) is  depending  upon  the  number  of  pulses  for  1  revolution of  the  rear  floor

roller.

3.4.2 Response

The Response function sets the frequency at which the system adjusts the control valve when reacting to a

change in forward speed.
Determining the correct setting is a method of trial and error as follows,

1.

With the Spreader stationary, from the SETUP page, press              and ENTER to begin a simulated speed.

2.

Run the Spreader in manual (‘MAN’) control mode and adjust the pressure down to a minimum.

3.

Switch to automatic (‘AUTO’) mode and observe the response.

If the application rate quickly rises and settles at the target rate then the response setting is correct.
A lower setting results in a slower response, and increases the time taken for the application rate to match the

target rate. A higher setting results in a faster response. If the application rate is unstable and varies about the

target rate, then the response setting may be too high.

Default: 100

Range: 0 - 9999

3.4.3 Deadband

The Deadband function sets the range over which the flow rate will vary about the target rate before the control

valve will respond.  A lower value will make the control respond to a smaller variation in spread rate and vice

versa. If the value is too low the system may be unstable about the target rate.

Default: 2.0

Range: 0 - 99.9

3.4.4 Startup Delay

As  the  spreader  starts  up,  it  can  take  a  number  of  seconds  for  all  pressure  pulses  to  balance  out.

Consequently the system takes some time to stabilise at the target rate.  The instrument must be stopped from

reacting to the initial flow surge.
Set the delay time to equal the time it takes for the Spreader system to reach normal working speed. When the

spreader section is switched on, the control valve will not operate for this time period.

Default: 2.0 seconds

Range: 0 - 99.5 seconds

3.5

Change PIN for Factory Configuration Menu

You  can  re-programme  your  own  PIN  for  this  menu.  Just  follow  the  screen  instructions. If  you  forget  your

personalised PIN, you will need to contact RDS for instructions.

3.

Factory Config.

7.

PIN # Change

Содержание Apollo FYM

Страница 1: ...1 Apollo FYM Spreader Controller Calibration RDS Part No Document Issue Software Issue S DC 500 10 746 1 1 20 2 14 PS605 001rev09...

Страница 2: ...sion Farming System the System are limited as set out in the specification of the System details of which are contained in the Help files and product literature and which must be read before using the...

Страница 3: ...e Smoothing 8 2 1 4 Off Target Alarm 8 2 1 5 Info Weight 8 2 2 Loadcell Correction 9 Correction Span 9 Min Stat Weight 9 Dynamic Time 9 Dynamic Weight 9 Start Delay 9 Steady Weight 9 H Land Delay 9 T...

Страница 4: ...dth 14 5 1 1 Set current Working Width 14 5 2 Forward Speed Sensor 14 5 2 1 Select Sensor Option 14 5 2 2 Wheel sensor calibration Autocal 14 5 2 3 Wheel sensor calibration manually calculating the Fo...

Страница 5: ...y Alpha numeric values are entered via the right hand keypad You must press the key from 2 to 5 times to select the required letter Some keys have additional special characters not shown on the key le...

Страница 6: ...he contrast setting is adjusted so that the screen graphics can no longer be viewed i e completely light or dark don t panic you can navigate directly to the DISPLAY screen by pressing and holding the...

Страница 7: ...press 1 5 Select Control Software There are two lines displayed If the head unit does not have a secondary software module fitted both lines will be the same and switching between them has no effect I...

Страница 8: ...it is acceptable for the instrument to display a steady readout of 10 tonnes ha between those limits i e 3 In this case the rate lock on figure should be set to 3 0 Adjustable from 0 to 50 Default 2...

Страница 9: ...tem will resume DYNAMIC corrections This is to give the floor time to get to speed T Factor Delay This is the pause time after each new DYNAMIC correction has been made before the new correction start...

Страница 10: ...nu function immediately sends the data to the serial port The message Printing Data is displayed while data transfer is occurring If the bar on the screen stops filling up part way the instrument cann...

Страница 11: ...speed If necessary measure this speed using a hand held tachometer Note the speed displayed on the INFO screen The correct Cal factor Initial Factor x Displayed Speed Actual Speed Default 1 pulse per...

Страница 12: ...get rate then the response setting may be too high Default 100 Range 0 9999 3 4 3 Deadband The Deadband function sets the range over which the flow rate will vary about the target rate before the cont...

Страница 13: ...Rate This is the target application rate that is programmed on the MAIN screen Default 20 Range 0 9999 4 1 3 T Factor The T factor is the calibration factor that is altered while the spreader is disp...

Страница 14: ...the forward speed sensor This could be calculated based on the nominal tyre diameter or rolling distance and then entered manually ref section 1 1 3 however this does not take into account wheel slip...

Страница 15: ...for exactly 10 revolutions of the sensed wheel Measure this distance in inches or metres and divide by 20 to find the Speed Sensor Factor iii If 4 wheel magnets are installed the distance is 1 4 the...

Страница 16: ...e ALARMS SETUP button at the base of the screen 6 1 1 Low High RPM Alarm From the RPM SETUP screen you can also set a minimum and maximum RPM at which an alarm is triggered Set as necessary Default 0...

Страница 17: ...APOLLO FYM SPREADER CONTROLLER 17 Issue 1 12 12 13 Original Issue Issue 1 1 20 2 14 Ref CRQ5468...

Отзывы: