Finned copper tube gas boilers & water heaters – Boiler Manual
46
COMBUSTION/SAFETY REPORT
FACTORY FIRE TEST REPORT:
Low Fire
High Fire
Manifold Gas Pressure: "WC"
Air Differential Pressure: "WC"
FIELD TEST REPORT IN STAGE:
1
2
3
4
Manifold Gas Pressure: "WC"
Air Differential Pressure: "WC"
Pilot Manifold Pressure: "WC"
CO
2
:
Stack Temp. (Net):
Efficiency @ °F Inlet Temp.
CO (PPM):
O
2
:
Stack Draft (Must Be Negative):
Pilot Signal:
SAFETY CONTROL CHECK:
Low Water Cut Off (PPM):
Factory Flow Switch
Operating Control
High Limit
Differential Air Switch STG. 1, 2
Differential Air Switch STG. 3, 4
Blocked Flu Switch
Flame Failure Lockout (CSD-1)
Pump Delay
Combustion Air Damper
Power Vent Proving Switch
Barometric Damper
COMMISSIONING THE UNIT
Customer Instructed?
Yes
No
All Covers Replaced?
Yes
No
Wiring Secure/Tight?
Yes
No
Customer Given Manual?
Yes
No
Cabinet Air Leaks?
Yes
No
Gas Leaks Detected?
Yes
No
Unit Cycled Min. of 15 X?
Yes
No
Temp. Set Per Customer?
Yes
No
Left Maintenance Instruction?
Yes
No
Commissioned By:
(Signature)
Date:
The delta T between the heaters inlet and outlet
is critical to proper flow. Before you leave the
job site you must record the delta T. This reading
should not exceed 35°F, 19.4°C or be lower than
20°F, 11.1°C.
Inlet
Temperature
Outlet
Temperature
Wired and Operating
Properly @ Setting:
Failed To Operate
Comment To Right
Comments
These results are affixed
to the side of the heater
on a small white label.