26
Maximum Equivalent Pipe Length (ft)
Natural Gas 1000 BTU/FT
3
0.60 Specific Gravity @ 0.5 in. WC Pressure Drop
Propane Gas 2500 BTU/FT
3
1.53 Specific Gravity @ 0.5 in. WC Pressure Drop
Input
3/4”
1”
1-1/4”
1-1/2”
Model (KBTU) N
P
N
P
N
P
N
P
410
399.0
*
15 20 55 95 225 215 480
4.6
**
6.1
**
16.8
**
29
**
68.6
**
65.5
**
146
**
*A 3/4” gas line can be used for up to 5’ (1.52 m) maximum length
from the gas valve in addition to the sediment trap.
** Dimension in meters.
PIPE SIZING FOR GAS CONNECTIONS
HEAT EXCHANGER PRESSURE DROP TABLES
Heat Exchanger with External Automatic Bypass
WATER FLOW
(GPM)
HEAD LOSS
(FT WC)
40 (151.4 LPM)
5.3 (1.32 kPa)
50 (189.3 LPM)
5.9 (1.47 kPa)
60 (227.1 LPM)
6.2 (1.54 kPa)
70 (265 LPM)
7.2 (1.79 kPa)
80 (302.8 LPM)
8.6 (2.14 kPa)
90 (340.7 LPM)
9.7 (2.42 kPa)
100 (378.5 LPM)
11.3 (2.81 kPa)
110 (416.4 LPM)
13.2 (3.29 kPa)
120 (454.2 LPM)
15.3 (3.81 kPa)
125 (473.2 LPM)
16.5 (4.11 kPa)
GAS PRESSURE ADJUSTMENT LOCATIONS
Fig. 14: Gas Valve
Table 8: Pipe Lengths for Gas Connections
Table 9: Heat Exchanger Pressure Drop
CAUTION:
The heater and its manual shut-off valve
must be disconnected from the gas supply during any
pressure testing of that system at test pressures in
excess of 1/2 psi (3.45 kPa). Dissipate test pressure
in the gas supply line before reconnecting the heater
and its manual shut off valve to gas supply line. FAIL-
URE TO FOLLOW THIS PROCEDURE MAY DAM-
AGE THE GAS VALVE. OVER PRESSURIZED GAS
VALVES ARE NOT COVERED BY WARRANTY. The
heater and its gas connections shall be leak tested
before placing the appliance in operation. Use soapy
water for leak test. DO NOT use open flame.
A minimum of 4” WC (1 kPa) and a maximum of
10.5“ WC (2.62 kPa) upstream pressure under load
and no-load conditions must be provided for natural
gas. A minimum of 12“ WC (3 kPa) and a maximum of
14“ WC (3.5 kPa) are required for propane gas under
load and no-load conditions, with no more than a 30%
pressure drop between static pressure and full load.
The factory manifold pressure settings should
be -2.0” ± 0.5” WC (0.5 ± 0.12 kPa) at high fire (7500
+/- 50 RPM fan speed) for either natural or propane
gas.
SUPPLY PRESSURES
NOTE:
Do not use Teflon tape on gas line pipe
thread. A pipe compound rated for use with natural
and propane gases is recommended. Apply sparing-
ly only on male pipe ends, leaving the two end
threads bare.
Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve locat-
ed outside the heater jacket. All gas piping should be
tested after installation in accordance with local codes.
Fig. 13: Gas Supply Connections
GAS SUPPLY CONNECTIONS
Содержание X94
Страница 24: ...24 Fig 10 Outdoor Venting Fig 11 3 in 1 Multi Vent Adapter ...
Страница 32: ...32 WIRING DIAGRAM Fig 26 Wiring Diagram ...
Страница 33: ...33 SECTION 4 SERVICING INSTRUCTIONS GENERAL LOCATION OF CONTROLS Fig 27 Location of Controls ...
Страница 46: ...46 SECTION 6 REPLACEMENT PARTS ...
Страница 47: ...47 ...
Страница 52: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A ...