34
Digital Temperature Control
The WH-101 thru WH-401 heaters can be equipped
with a Raypak digital temperature control. For opera-
tion with this control, refer to the Temp-Tracker
Installation and Operating Instructions, Raypak
Catalog number 5000.66 (P/N 241177).
High Limit (Manual Reset)
The heater is equipped with a manual reset high limit
temperature device. If the optional adjustable limit is
used, push the reset button and adjust the setting to
30°F or 40°F above desired operating temperature.
High Limit — Auto Reset
(Optional)
This heater may be equipped with an optional adjust-
able auto reset high limit temperature device.
Fig. 29: Manual Reset High Limit
Fig. 28: Digital Temperature Control
Direct Domestic Hot Water
In this configuration the controller will operate to main-
tain a set temperature in the storage tank. The
differential is fixed at 5F below target. The System
Supply Sensor (S2) is used as the operating sensor.
Boiler Outlet Sensor (S1) is used for boiler outlet max-
imum limiting. Boiler Pump (P1) is controlled by the
boiler and is cycled off using a 5 minute fixed purge
delay after burner operation has ceased.
The DIP switch settings are as follows:
DIP 1 ON (ON/OFF) – OFF (2-STAGE)
DIP 2 OFF (SETPOINT)
DIP 3 OFF (WWSD INACTIVE)
DIP 4 ON (160°F BOIL MAX)
DIP 5 OFF (DIRECT DHW)
Fig. 27: Direct Domestic Hot water
Содержание HI DELTA HD401
Страница 36: ...36 WIRING DIAGRAM MODELS HD101 HD151 TYPE WH...
Страница 37: ...37 WIRING DIAGRAM MODELS HD101 HD151 TYPE H...
Страница 38: ...38 WIRING DIAGRAM MODELS HD201 HD401 TYPE WH...
Страница 39: ...39 WIRING DIAGRAM MODELS HD201 HD401 TYPE H...
Страница 50: ...50...
Страница 51: ...51...
Страница 52: ...52 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...