46
RESET RATIO
The control uses the four following settings to determine the reset ratio:
Boiler Start (Boil START)
The Boil START temperature is the theoretical boiler supply water temperature that the heating system requires when the outdoor air
temperature equals the OUT START temperature setting. The Boil START is typically set to the desired building temperature.
Outdoor Start (OUT START)
The OUT START temperature is the outdoor air temperature at which the control provides the Boil START water temperature to
the system. The OUT START is typically set to the desired building temperature.
Outdoor Design (OUT DESIGN)
The OUT DESIGN is the outdoor air temperature that is the typical coldest annual temperature where the building is located. This
temperature is used when completing heat loss calculations for the building.
Boiler Design (Boil DESIGN)
The Boil DESIGN temperature is the water temperature required to heat the boiler zones when the outdoor air is as cold as the
OUT DESIGN temperature.
Warm Weather Shut Down (WWSD)
When the outdoor air temperature rises above the WWSD setting, the
control turns on the WWSD segment in the display. When the control is in
Warm Weather Shut Down, the Dem 1 segment is displayed if there is a
heat demand. However, the control does not operate the boiler to satisfy
this demand. The control continues to respond to DHW demands.
Decreasing Outdoor Temperature
In
cr
ea
sin
g
W
at
er
T
em
pe
ra
tu
re
Boil
START
OUT
DESIGN
Boil DESIGN
START
OUT
Reset Ratio
The controller uses the following four settings to cal-
culate the Reset Ratio (RR):
For example, when using the default values, the RR
is:
RR = (70 - 10) / (180 - 70) = 0.55
Therefore, the RR is 0.55:1 (Outdoor:Water).
RESET RATIO =
(OUTDOOR START – OUTDOOR DESIGN)
(BOILER DESIGN – BOILER START)
Fig. 45: Reset Ratio
Содержание 88AR-398A
Страница 18: ...18 Fig 13 MODE 1 Single Boiler Primary Secondary Piping...
Страница 19: ...19 Fig 14 MODE 2 Single Boiler Primary Secondary Piping with Indirect DHW on System Loop...
Страница 20: ...20 Fig 15 MODE 3 Single Boiler Primary Secondary Piping with Indirect DHW on Boiler Loop...
Страница 47: ...47 WIRING DIAGRAM Fig 46 Wiring Diagram...
Страница 54: ...54 Fig 55 Boiler Lighting Shut Off Instructions...
Страница 65: ...65 ILLUSTRATED PARTS LIST...
Страница 66: ...66...
Страница 67: ...67...
Страница 68: ...68 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...