Table Q: Adjust Menu
Item
Application
Range
Description
Default
User
TARGET
MODE 1, 2, 3
RSET <> SETP
RSET = Outdoor Reset, SETP =Setpoint
SETP
MODE
MODE 1, 2, 3
1, 2, 3
Piping and application configuration.
1
SETPOINT MODE 1, 2, 3
50°F to 192°F
Boiler target temperature while a heat
demand is present for setpoint operation
180°F
OUT START MODE 1, 2, 3
35°F to 85°F
Outdoor starting temperature - outdoor reset
70°F
OUT DESIGN MODE 1, 2, 3
-60°F to 45°F
Outdoor design temperature - outdoor reset
10°F
Boil START MODE 1, 2, 3
35°F to 150°F
Starting boiler target temperature when the
outdoor temperature is at outdoor start out-
door reset
70°F
Boil DESIGN MODE 1, 2, 3
70°F to 200°F
Design boiler target temperature when the
outdoor temperature is at outdoor design
outdoor reset
180°F
TARGET MAX MODE 1, 2, 3
100°F to 192°F
Maximum target system temperature
192°F
TARGET MIN MODE 1, 2, 3
OFF, 50°F to 190°F
Minimum target system temperature
50°F
TARGET DIFF MODE 1, 2, 3
2°F to 42°F
Differential for target system temperature
10°F
IND SENSOR MODE 1, 2, 3
OFF <> ON
Selects whether a DHW sensor is used for
indirect DHW tank
OFF
IND SETP
MODE 2, 3
OFF, 50°F to 180°F
Target Indirect DHW Tempererature (IND
Sensor = ON, to enable this setting)
140F
DHW DIFF
MODE 2, 3
2°F to 10°F
Differential for the target indirect DHW tank
temperature, Requires IND Sensor = ON
6°F
IND SUPPLY
MODE 2, 3
OFF, 50°F to PIM value*
Target boiler temperature for the DHW heat
exchanger during indirect DHW operation,
requires IND Sensor = OFF
180°F
DHW
PRIORITY
MODE 2
OFF <> ON
Selects whether or not Indirect DHW priority
is active during indirect DHW operation
OFF
PRI OVR
MODE 2, 3
Au, 0:10hr to 2:00hr
Sets the length of the indirect DHW priority
override time
1:00hr
SYS PURGE
All
OFF, 0:20min to 20:00min
Sets the length of the system pump post
purge
20
seconds
MIX TYPE
All
H (BOIL <> PLNT)
Selects the type of control depending on
pipe configuration for CWP
H BOIL
MIX TARGET
All
50°F TO 140°F
Inlet Target Temperature
120F
MIX LOCK
All
ON <>OFF
The equipment will trigger a warning when
“MIX Target” is not reached within 7 min-
utes. MIX LOCK = ON Alarm and lockout,
MIX LOCK = OFF Alarm only
OFF
MIX TRIM
All
-5 to 5
This adjustment is for various types and
sizes of units as well as various actuator
motor speeds and types supplied by Raypak
0
MIX SPEED
All
FAST <> MED <> SLOW
This setting defines speed of response.
MED
MIX INV
All
ON <>OFF
This option is related to the use of spring
return actuators with a proportional valve
OFF
WWSD
MODE 1, 2, 3
40°F to 100°F
The system warm weather shutdown tem-
perature outdoor reset, requires TARGET =
REST
70°F
UNITS
All
deg F <> deg C
Show units using icons in display
deg F
MODBUS
All
OFF<>MNTR<>TEMP<>RATE
ModBus Operating Mode: Off, Monitor, Temp
Control, Rate Control
OFF
ADDRESS
All
1 to 247
ModBus slave address
1
DATA TYPE
All
RTU <> ASCI
Modbus data type
RTU
BAUD RATE
All
2400<>9600<>19K2<>57K6<>115K
19K2
PARITY
All
NONE<>EVEN<>ODD
EVEN
* Fixed values based on the ID card.
Содержание 88AR-398A
Страница 18: ...18 Fig 13 MODE 1 Single Boiler Primary Secondary Piping...
Страница 19: ...19 Fig 14 MODE 2 Single Boiler Primary Secondary Piping with Indirect DHW on System Loop...
Страница 20: ...20 Fig 15 MODE 3 Single Boiler Primary Secondary Piping with Indirect DHW on Boiler Loop...
Страница 47: ...47 WIRING DIAGRAM Fig 46 Wiring Diagram...
Страница 54: ...54 Fig 55 Boiler Lighting Shut Off Instructions...
Страница 65: ...65 ILLUSTRATED PARTS LIST...
Страница 66: ...66...
Страница 67: ...67...
Страница 68: ...68 www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...