5973129-9
LOGIC BOARD PROGRAMMING
The logic board is programmed at the factory with constant pressure to open and close. Follow the instructions
below to program the board for your application.
Programming Notes:
1. Use the Open, Close and Stop buttons on the board when programming.
2.
Open button
used to
increase time
or turn functions '
On
' & '
Off
'.
3.
Close button
used to
decrease time
or
page
through choices.
4.
Stop button
used to
continue
to next option and
end
programming.
1. To start the program mode, locate the program and stop button on the logic board (see figure 12), press
and hold both program and stop buttons for 5 seconds.
2. "
PROGRAMMING FIRMWARE
" will display briefly followed by "
PROGRAMMING CONFIGURATION
", then
"
WIRING MODE
" will display. There are three options to choose from as shown below.
NORMAL SR5
- 3 button momentary contact on open, close, and stop with 1 second delay on open and close
with provisions for connection of a reversing device(s).
CSTP OPN/CLS RD
- Constant pressure to open and close.
CSTP CLS ONLY RC
- 3 button momentary contact on open and stop, constant pressure to close.
3. Select the wiring type by using the
close button
to page through the wiring modes. Press the
stop button
to
continue
to the next option.
4. "
SENSOR 1 TYPE
" will display, there are two options to choose from, "
PHOTO EYE
" or "
ELECTRIC EDGE
".
Use the
close button
to page through the choices. Press the
stop button
to
continue
to the next option.
When using
RD
or
RC
wiring, photo eye's or edge must be selected even though they are not required.
Note: The photo eye or an electric edge must be monitored.
5. "
SENSOR 2 TYPE
" will display, there are three options, "
NONE CONNECTED
", "
PHOTO EYE
", or
"
ELECTRIC EDGE
". Use the
close button
to page through the choices. Press the
stop button
to
continue
to
next option.
Note: The photo eye or an electric edge must be monitored.
If wiring type is RC or RD, this is the end of the programming steps. If SR5 wiring is selected continue to step 6.
6. "
TIMER TO CLOSE
", this will display only if there is a jumper connected on
JS3
or a switch connected to
J3
&
J4
of the logic board.
The timer to close can be set from 10 seconds to 240 seconds in 1 second intervals.
Use the open and close buttons on the board to set the time. Press the
stop button
to
continue
to the next option.
7. "
AUX INPUT 1 TYPE
" will display. There are five options to choose from as shown below. Use the
close
button
to page through the choices. Press the
stop button
to
continue
to next option.
NONE CONNECTED
- No device required
REVERSING (N.C.)
- Non-monitored, normally closed reversing device.
REVERSING (N.O.) -
Non-monitored, normally open reversing device.
VENTILATION (N.O.)
- A normally open contact, such as a carbon monoxide detector, may be used to open
the door for ventilation. The door can be opened to a determined height by setting the
open run time. See #8.
FIRE STATION (N.O.)
- A normally open contact, such as a pull cord, can be used to open the door. The door
will fully open and then close after a determined time has been set. The door will only
time out and close, if opened from the auxilary input. See #9.