5973129-9

LOGIC BOARD PROGRAMMING

The logic board is programmed at the factory with constant pressure to open and close.  Follow the instructions
below to program the board for your application.

Programming Notes:

     1. Use the Open, Close and Stop buttons on the board when programming.
     2.

Open button

 used to

 increase time

 or turn functions '

On

' & '

Off

'.

     3.

Close button

 used to

decrease time

 or

page

 through choices.

     4.

Stop button

 used to

continue

to next option and

end

 programming.

1. To start the program mode, locate the program and stop button on the logic board (see figure 12), press
    and hold both program and stop buttons for 5 seconds.

2. "

PROGRAMMING FIRMWARE

" will display briefly followed by "

PROGRAMMING CONFIGURATION

", then

    "

WIRING MODE

" will display. There are three options to choose from as shown below.

NORMAL SR5

- 3 button momentary contact on open, close, and stop with 1 second delay on open and close

     with provisions for connection of a reversing device(s).

CSTP OPN/CLS RD

- Constant pressure to open and close.

CSTP CLS ONLY RC

- 3 button momentary contact on open and stop, constant pressure to close.

3.  Select the wiring type by using the

close button

 to page through the wiring modes. Press the

stop button

 to

   continue

to the next option.

4.  "

SENSOR 1 TYPE

" will display, there are two options to choose from, "

PHOTO EYE

" or "

ELECTRIC EDGE

".

     Use the

close button

 to page through the choices. Press the

stop button

 to

continue

to the next option.

When using

RD

 or

RC

wiring, photo eye's or edge must be selected even though they are not required.

           Note: The photo eye or an electric edge must be monitored.

5.  "

SENSOR 2 TYPE

"  will display, there are three options, "

NONE CONNECTED

", "

PHOTO EYE

", or

     "

ELECTRIC EDGE

". Use the

close button

 to page through the choices. Press the

stop button

 to

continue

 to

     next option.

            Note: The photo eye or an electric edge must be monitored.

 If wiring type is RC or RD, this is the end of the programming steps. If SR5 wiring is selected continue to step 6.

6.  "

TIMER TO CLOSE

", this will display only if there is a jumper connected on 

JS3

 or a switch connected to 

J3 

J4

of the logic board.

     The timer to close can be set from 10 seconds to 240 seconds in 1 second intervals.

     Use the open and close buttons on the board to set the time. Press the 

stop button 

to 

continue 

to the next option.

7.  "

AUX INPUT 1 TYPE

" will display. There are five options to choose from as shown below. Use the

close

   button

 to page through the choices. Press the

stop button

 to

continue

 to next option.

NONE CONNECTED

- No device required

REVERSING (N.C.)

- Non-monitored, normally closed reversing device.

REVERSING (N.O.) -

Non-monitored, normally open reversing device.

   VENTILATION (N.O.)

- A normally open contact, such as a carbon monoxide detector, may be used to open

   the door for ventilation. The door can be  opened to a determined height by setting the

                                           open run time. See #8.

FIRE STATION (N.O.)

- A normally open contact, such as a pull cord, can be used to open the door. The door
  will fully open and then close after a determined time has been set. The door will only

       time out and close, if opened from the auxilary input. See #9.

Содержание ControlHoist 2.0 STANDARD

Страница 1: ...ist 2 0 PLEASE READ THESE INSTRUCTIONS BEFORE STARTING INSTALLATION IT IS IMPORTANT THAT THIS OPERATOR BE INSTALLED CORRECTLY IN ORDER TO ACHIEVE SAFE AND PROPER OPERATION THIS OPERATOR HAS BEEN SUPPL...

Страница 2: ...replace the defective door components Labor charges for installations or repairs shall be the responsibility of the consumer and must be performed by an authorized Raynor Dealer This warranty extends...

Страница 3: ...s 9 Do not place hands in area of pulleys V belt sprockets chain or rotating shafts 10 Install warning placard on wall next to push button 11 Attach instruction booklet to wall near push button 12 Do...

Страница 4: ...ify delivering VISUAL INSPECTION carrier immediately rail assembly with lug B facing the open end of the rails ing packing material Unpack powerhead and trolley rail assemblies being 5973129 4 electri...

Страница 5: ...ng either lag screws or self tapping screws furnished in hardware package Resting powerhead of operator on floor attach front end of rails to front mounting bracket Swing unit into position over door...

Страница 6: ...e and operator voltage shown on the cover are the same 5973129 6 TO PRE VEN T ENT RAP MEN T Do not sta rt doo r dow nwa rd unle ss doo rwa y is clea r WAR NIN G W AR NING ATTACH DOOR BRACKET Some inst...

Страница 7: ...14 14 12 14 10 14 8 14 6 12 0 5 115 230 14 14 12 14 10 14 8 14 6 12 0 75 115 230 12 14 10 14 8 14 6 12 4 10 1 115 230 12 14 10 14 8 14 6 12 4 10 1 5 230 14 14 12 10 8 MINIMUM WIRE SIZE FOR SINGLE PHA...

Страница 8: ...minal Block 1 Terminal Block 2 High Voltage Wire Harness Connection LIGHT CCM NO1 SER C1NC1 NO2 C2NC2 ON OFF OPEN CLOSE ON OFF 24VDC 24VDC 24VAC 24VAC Terminal Block 3 24V DC Power Connection Auxiliar...

Страница 9: ...sing RD or RC wiring photo eye s or edge must be selected even though they are not required Note The photo eye or an electric edge must be monitored 5 SENSOR 2 TYPE will display there are three option...

Страница 10: ...OFF If a warning light is required select ON Press the stop button to continue 16 If a warning light is ON WARNING TIME will display The time is set in 1 second intervals from 3 seconds to 10 seconds...

Страница 11: ...r death 8 SAVE THESE INSTRUCTIONS OPERATING INSTRUCTIONS Operating the 3 Button Control Station 1 Press OPEN button The door should move in the open direction 2 Press STOP button The door should stop...

Страница 12: ...eck manual operation of door Refer to installation instructions 800 page 5972558 1 for guidelines Test all reversing devices once a month for proper operation Test all accessories that may have been s...

Страница 13: ...ng Off Stop button pressed or NOT connected On Open button sending signal pressed Off Open button is not sending signal 2 Open D12 6 I Lock D24 7 I Lock D23 On Chain hoist interlock circuit is open ch...

Страница 14: ...en limit switch and the open button is pushed This message will display anytime the board is not receiving a signal from the sensor 2 when close button is pressed Whether it is not connected activated...

Страница 15: ...minate stress on rollers and cables 1 Sunlight is blocking the receiving photo eye 2 Faulty photo eyes 1 Connect Operator to power source 2 Check voltage at L1 L2 for single phase and at L1 L2 L3 for...

Страница 16: ...oard Verify power consumption of the device s before installing You may have to power the device from an external power source using only the contacts of the device to activate the operator 3 The comm...

Страница 17: ...use the dry contacts of that relay to activate the device If more than 3 amps of power is being consumed through the auxiliary board then damage to the board may occur 2 There is a 14 pin connector o...

Страница 18: ...lied With Raynor Door NOTE Placement of Labels may vary from what is shown Spring Warning Tag Push Button Placard Locate Near Push Button Door Safety Label Bottom Fixture Danger Label Bottom Fixture D...

Отзывы: