(2) Check whether the load is in compliance with
the specification; (3) Contact customer service if
error warning continues.
INV DC Over
F11
(1) Restart the inverter and wait until it functions
normally.
(2) Contact customer service if error warning
continues.
NTC/Sink Temp
Over
F12
F13
(1) Restart the inverter, restart the machine after a
few minutes of cooling, and observe whether the
machine can return to normal.
(2) Check if the ambient temperature is outside the
normal operating temperature range of the
machine.
(3) Contact customer service if error warning
continues.
Dischg Curr Over
F15
(1) Wait one minute for the inverter to restart;
(2) Check whether the load is in compliance with the
specification; (3) Contact customer service if error
warning continues.
CHG Current Over
F16
(1) Check if battery wiring port is short circuited;
(2) Check if charging current is in compliance with
presetting;
(3) Contact customer service if error warning
continues.
Current Sensor Fault
F17
(1) Restart the inverter and wait until it functions
normally.
(2) Contact customer service if error warning
continues.
INV Abnormal
F18
(1) Please contact the distributor.
Communication
Fault
F32
(1) Restart the inverter and wait until it functions
normally.
(2) Contact customer service if error warning
continues.
Grid Fault
W00
W01
W02
W03
(1) Check if the local voltage and frequency is in
compliance with the machine specification;
(2) If voltage and frequency are within the accepted
range, then wait 2 minutes for the inverter to function
normally; but if no recovery or fault repeats, please
contact the local inverter customer service;
(3) Contact the local power company if voltage and
frequency are beyond range or unstable.
Solar Loss
W04
(1) PV is not connected;
(2) Check grid connection;
(3) Check PV availability.
Bat Loss
W05
(1) Battery is not connected;
(2)
Check if battery wiring port is short circuited;
(3) Contact customer service if error warning
continues.
Bat Volt Low
W06
W07
(1) Check the battery availability;
(2) Contact customer service if error warning
continues.
Types
Codes
Solutions
Bat Volt High
W08
(1) Check if the battery is in line with the presetting;
(2) If so, power off and restart;
(3) Contact customer service if error warning
continues.
Over Load Warning
W09
(1) Wait one minute for the inverter to restart;
Telephone : +44 (0) 1245 428500
Email : [email protected]
Page 47