site. Wiring sizing to be in accordance with local wiring regulations
. Please make AC cables on
There are"L" "N'' '' '' symbols marked inside the connector, the Line wire of grid must
be connected to "L" terminal; the Neutral wire of grid must be connected to "N" terminal;
the Earth of grid must be connected to '' ''
Object
Description
Value
A
External diameter
12mm to 18mm
B
Copper conductor cross-section
4mm² to 10mm²
C
Stripping length of the insulated conductors
approx.13mm
D
Stripping length of the outer sheath of the AC cable
approx.53mm
The PE conductor must be 10mm longer than the L and N conductors
b. Insert the conductor into the suitable ferrule acc. to DIN 46228-4 and crimp the contact.
b
c. Unscrew the swivel nut from the threaded sleeve and thread the swivel nut and threaded sleeve over the
AC cable.
c
Telephone : +44 (0) 1245 428500
Email : [email protected]
Page 23
d. Insert the crimped conductors L, N and PE into the corresponding terminals and tighten the screw with a
hex key wrench screwdriver (size:2.5, 1.2-2.0N.m). Ensure that all conductors are securely in place in the
screw terminals on the bush insert.
d
3.2.1 Wiring and connections