Step 4 Set charging parameter on the battery charger.
Case #1, One battery PACK is charged. Set the charge limited voltage 56.5V; Set the charge limited current
50A;
Case #2, Two ~ Five battery PACKs are charged. Set the charge limited voltage 56.5V; Set the charge limited
current 100A;
Step 5 After the battery is
charged, switch off the battery charger and then the battery DC breaker.
Disconnect the DC cables and then press the battery “ start key”
for 3 second to switch off the battery
PACK.
Page 42
6.4 Recharge Operation Steps
Step 1 Connect power cables to the battery charger correctly. The maximum number of battery PACK
connected parallel is 5.
Step 2 Turn on the battery PACK DC breaker to ON; Press the battery “ start key” for 3 second to start the
battery PACK. Check the LED on the battery PACK is on.
Step 3 Turn on the battery charger.