51
Menu
Level 1
Menu
Level 2
Menu
Level 3
Menu
Level 4
Menu
Level 5
Menu Level
6
Default
Selection
Comment
GRID
POWER
0…100%
100%
Limit or increase the power
exported from the system to
the grid.
INV
VOLT
MAX
VOLT(S
1)
set upper
limit voltage
280Vac
These settings should not be
altered. They are set
automatically according to the
country selected within Grid
Setting. If the inverter sees
that these values have been
reached, or exceeded, then
the inverter will stop
generating.
set
protection
time
1000ms
VOLT(S
2)
set upper
limit voltage
285Vac
set
protection
time
400ms
INV
VOLT
MIN
VOLT
(S1)
set lower
limit voltage
150Vac
set
protection
time
1000ms
VOLT
(S2)
set lower
limit voltage
120Vac
set
protection
time
400ms
INV
FREQ
MAX
FREQ
(S1)
set upper
limit
frequency
55Hz
set
protection
time
500ms
FREQ
(S2)
set upper
limit
frequency
55Hz
set
protection
time
500ms
INV
FREQ
MIN
FREQ
(S1)
set lower
limit
frequency
45Hz
Содержание RI-ENERGYFLOW-3P-MODULAR...
Страница 4: ...4...
Страница 12: ...12 Accessory Cable PACK10 2 Accessory Cable PACK20 4 Accessory Cable PACK30 6...
Страница 13: ...13 Accessory Cable PACK40 8...
Страница 14: ...14...
Страница 28: ...28 Figure 17 Wiring the Communication Cable...
Страница 30: ...30 Figure 19 PV Wiring Step12 Close the lid and tighten the screw Figure 20...
Страница 58: ...58...