49
Menu
Level 1
Menu
Level 2
Menu
Level 3
Menu
Level 4
Menu
Level 5
Menu Level
6
Default
Selection
Comment
Enable
up and check the state of
charge and depth of
discharge at the interval set.
Time
Set time
If time is selected the user
will be prompted to enter a
value 0…300 minutes.
Heating
FLIM
Automatic
Automatic
Allows the user to enable or
disable the heating film
installed within the battery
modules. Automatic means
the system measures the
Outside temperature and
turns the film on as needed.
Only applicable if heating film
is requested at time of
ordering.
ON
OFF
BMS
DOD
Disable
Disable
Leave disabled. The inverter
will monitor depth of
discharge.
Enable
Maintain
SOC
Disable
Enable
Disable: The minimum SOC
will not be maintained.
Enable
Enable: The minimum SOC
2% is maintained. When the
battery SOC is less than 2%,
the grid charges the battery
pack to 5% through the
inverter.
Force
Wake
Disable
Disable
Enabling this option means
the battery will always remain
online and will not go to
sleep.
Enable
Grid
STD
1.China
Local
Allows the user to select the
country that the system is
installed in.
2. Germany
3.
Australia
AUS-A
AUS-B
AUS-C
4. Italy
CEI0-21
CEI0-21 ACEA
Содержание RI-ENERGYFLOW-3P-MODULAR...
Страница 4: ...4...
Страница 12: ...12 Accessory Cable PACK10 2 Accessory Cable PACK20 4 Accessory Cable PACK30 6...
Страница 13: ...13 Accessory Cable PACK40 8...
Страница 14: ...14...
Страница 28: ...28 Figure 17 Wiring the Communication Cable...
Страница 30: ...30 Figure 19 PV Wiring Step12 Close the lid and tighten the screw Figure 20...
Страница 58: ...58...