46
Normal Condition
:
X =
S
(Amps) x ____ Hrs. (Backup time
required)
X=(50x10^-3)*48hrs = 2.4
Fire current (
F
) = Max. NAC Current = 600mA @ 5 min [5/60]
=0.0833hr
Alarm Condition
:
Y =
F
(Amps) x ____ Hrs. (Backup time
required)
Y=(600x10^-3)*0.0833hr(5min)=0.04998
Battery Ah required :
AH = (X + Y) x 1.2 (Derating Factor).
AH=(2.4 + 0.04998)*1.2 = 2.939
Note:
Refer specification (Page 12) for Quiescent, standby, alarm
currents
Chapter 8: Trouble Shooting