Turn off the Internal Buzzer.
Turn off the External NAC’s.
Turn on the silenced LED in the repeater panel only.
NOTE:-
While Pressing the Silence key in the Main panel, it will silence
the both NAC’s in main panel and repeater panel.
But while pressing the silence key in Repeater panel (Passive), it
silences the NAC’s connected in Repeater panel only.
If the repeater (Active), it silences the NAC’s connected in both
repeater & Main panel.
5.3.3
Supervisory:
When the main panel detects supervisory signal via
the any normally open contact devices, the repeater
panel will replicate the same in the repeater panel.
Turn on the panel buzzer with toggle tone.
The common supervisory LED will glow.
The LCD screen for panel model [RE-2554, RE-2558] will
be as below.
The above screen
Pn P
does not take place for RE-
120GR & RE- 25AR.
In case of multiple zone supervisory, the origin zone and
recent zone supervisory LED will be viewed in LCD
screen is same as above.
X
– index no. of supervisory event;
Y
– Total no. of supervisory
events;
Pn
– Panel;
P
- Denotes the Panel Address.
Supervisory [x/y]
Pn P
ZoneZ