background image

BSR-

615

7   

Page

 1

 from

 4

921

6

1

57

00_0

9

_00

3

GENERAL

The user have to read carefully the following instructions, in order to be properly informed and keep them 
for future use.

The 

BSR-6

1

5

7 is an analogue addressable smoke detector which integrates functions of optical smoke 

and heat detection and

 

it can work with any fire panel supports Olympia A Protocol. It can be adjusted to 

detect multiple levels of smoke and heat offering flexibility and rich functionality. Also, it integrates a short 
circuit  isolation  circuit  which  is  automatically  activated  and  disconnects  the  defective  node  from  the 
remaining loop, allowing it to be located by the panel.
The detector sends to the main panel an analogue value which depends on the concentration of smoke 
and heat. The value is 100 in concentration of 0.107dB/m (small amount of smoke) or a temperature of 

o

o

57 C

 

and increases proportionally to 120 in concentration of 0.300dB/m or a temperature of 90 C. When a 

sudden increase in temperature is detected the detector sends the value of 121.
By default the panel is set to sound an alarm when the concentration of smoke is 0.107dB/m or the 
temperature is 57 C. The user can change this setting from the panel for each detector and define any 
level  of  smoke  concentration  or  temperature  between  the  lower  and  the  upper  limits,  specifying  the 
sensitivity of the system depending on the requirements of each site. Also, the user can select A1R

 

or A2S 

working mode through the panel.
They are composed by two parts. A plastic base which is placed on the ceiling and the main body of the 

o

detector which fits on the plastic base with a simple rotation to the right. The detectors have a 360  visible 
led and a remote led driver which are light up constantly in case of detection of fire, till cancelled from the 
panel. Also, they are staying lit even if the sirens are silenced from the panel, so the detector which 

o

1

4

0

μΑ

11-30

V DC

TEMPERATURE SENSITIVITY

SMOKE CONCENTRATION SENSITIVITY

1A

5

A

IP

4

2

100

m

Ω

2.5mA (with

 

activated LED)

Adjustable from 0.1

07 

to

 0

.

300

 in 

0

.

010 

dB/m steps

Adjustable from

57 

to

 90 

in 

1

.

5

 steps

 

o

C

10.7 - 12.7

9.3 - 10.6

Up to

 95%

ο

-

40 

to

 7

0

  C

ABS/PC

160 

gr

.

103 (

d) x 

55

 (h) mm

years

Remote

 

LED driver

Alarm LED

INDICATORS

OUTPUT

Analogue addressable optical smoke and

rate-of-rise heat detector with integrated isolator

TECHNICAL CHARACTERISTICS

MAIN VOLTAGE

STANDBY CONSUMPTION

ALARM CONSUMPTION

MAXIMUM LOOP CURRENT

 (

Ic max, -L in/out)

MAXIMUM SWITCH CURRENT

 (

Is max, -L in/out)

MAXIMUM SERIES RESISTANCE

 (

Zc max, -L in-out

)

MAXIMUM LEAKAGE CURRENT
IN ISOLATION MODE 

(

I max, -L in/out

)

L

 

ISOLATION VOLTAGE

 (

Vso min-max

)

RECONNECT VOLTAGE

 (

Vsc min-max

)

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

OPERATING TEMPERATURE RANGE

RELATIVE HUMIDITY

CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT

GUARANTEE

2

5mA pulses (6ms duration every 

2

sec)

Thank you for your trust in our products  

Olympia Electronics - European manufacturer

EN 54-5 EN 54-7 EN 54-17

,

CLASS

A1R/A2S

Olympia A Protocol

COMMUNICATION PROTOCOL

Содержание BSR-6157

Страница 1: ...o the user can selectA1R orA2S working mode through the panel They are composed by two parts A plastic base which is placed on the ceiling and the main body of the o detector which fits on the plastic base with a simple rotation to the right The detectors have a 360 visible led and a remote led driver which are light up constantly in case of detection of fire till cancelled from the panel Also the...

Страница 2: ... more than 15m Also they must be placed at least 50 cm away from fluorescent lamps Cable diameter should be from to MAINTENANCE FUNCTIONALTESTING The detector has fault diagnosis and dust compensation functions which automatically informs you when replacement or cleaning actions are required These functions combined with periodic manual testing ensure maximum security level The manual testing proc...

Страница 3: ...ce and after 3 5 seconds it is ready for operation CONNECTION 1 IN OUT Connect to L of the loop 2 IN Connect to L of the loop 3 OUT Connect to L of the loop 4 R External LED connection 5 Connected to the cable s shield when shield is used Mounting base Figure 1 5 5 R R Installation process 2 Connection with exterrnal LED UT O N I N I T U O Side marks Page 3 from 4 eni t n s g a f d t e n ta e c m ...

Страница 4: ... any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or replacement as long as the warranty period is valid Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of def...

Отзывы: