background image

9060 High Voltage Controller - Operation 

31 

CP-13-05.3 

DI/DT CONFIGURATION 

(For 80100-51X Units Only)

 

The 9060 Voltage Controller, model 80100-51X, 
for  use  with  the  ATEX  approved  Aerobell  168 
applicator,  contains  a  di/dt  (rate  of  change  in 
current  with  respect  to  time)  safety  overload 
fault  and  is  used  in  addition  to  the  standard 
current  overload  fault.    This  is  an  adjustable 
setting  which  determines  the  maximum  current 
increase  that  can  occur  during  a  specific  time 
period.    Both  the  time  period  and  sensitivity  of 
the  di/dt  configuration  can  be  adjusted  to 
maximize detection. 
 
The  di/dt  detection  feature  improves  the  ability 
of the power supply to prevent discharges from 
the  applicator  to  a  grounded  object  when  the 
object  is  approaching  the  applicator  at  fast 
speeds.    Slow  rates  of  approach  are  typically 
sensed  by  the  current  overload.    The  di/dt  and 
current  overloads  must  be  set  correctly  to 
prevent discharges.  
 
The  controller  monitors  the  output  current 
values  and  compares  the  average  rate  of 
change  over  the  selected  time  interval  to  the 
user  specified  settings  to  determine  if  a  fault 
condition  has  occurred.    If  a  fault  occurs,  the 
unit  with  turn  off  the  high  voltage  and  display 
the  “dOL”  fault  code  as  shown  in  the  “Fault 
Descriptions” section of this manual.  

(For 80100-51X Units ONLY) 

 

Every

 time the high voltage is triggered 

(turned on), there is a 4 second timer that 

inhibits the DI/DT overload fault 

while 

the applicator is being charged.  Ensure 
that NO OBJECTS approach the bell dur-
ing charging. 

                      

 

W A R N I N G 

Adjusting DI/DT Parameters 

The  di/dt  safety  overload  fault  is  configured 
based  upon  two  (2)  parameters;  Sensitivity 
(SE),  and  Sample  Time  Interval  (SA).    These 
parameters  can  be  adjusted  in  the  Parameter 
Adjustment  Mode.    Refer  to  the  “Parameter 
Adjustment  Mode”  portion  of  the  “Operation” 
section  of  this  manual  for  information  on 
adjusting these parameters. 
 
The  sensitivity  (SE)  parameter  determines  the 
amount of current change that must be exceed-
ed  during  the  sampling  time  interval.    The 
following table specifies the average amount of 
current change that must occur during the time 
interval  to  produce  a  fault  based  on  each  SE 
setting. 

Sensitivity Values 

SE Setting 

Average Rate of Change  

(per sampling interval) 

(Most Sensitive) 2.0 

4uA 

3.0 

6uA 

4.0 

8uA 

5.0 

10uA 

6.0 

12uA 

7.0 

14uA 

8.0 

16uA 

9.0 

18uA 

10.0 

20uA 

11.0 

22uA 

(Least Sensitive) 12.0 

24uA 

The  sample  time  interval  (SA)  parameter 
determines the number of samples that must be 
collected  before  a  rate  of  change  calculation  is 
performed.  This parameter can be set from 2 to 
50  with  a  sample  taken  every  10  ms.  This 
produces  a  sample  time  interval  range  from 
20ms  to  500ms.    Using  a  larger  time    interval 
produces  a  di/dt  configuration  that  is  less 
sensitive  to  current  spikes  which  are  averaged 
out  over  the  sample  time  interval  and  can  be 
used to remove nuisance faults. 

Содержание 80100 Series

Страница 1: ...page 1 and all instructions in this manual Keep this Service Manual for future reference Service Manual Price 50 00 U S Service Manual Price 50 00 U S Service Manual Price 50 00 U S Service Manual Pri...

Страница 2: ...CP 13 05 3...

Страница 3: ...RS 11 12 FUSES 12 SPARE FUSES 12 LOCAL REMOTE BOARD 12 SIGNAL INTERFACE LOCAL MODE 13 SIGNAL INTERFACE REMOTE MODE 13 16 INSTALLATION 17 28 GENERAL INFORMATION 17 LOCATION OF THE 9060 17 ELECTRICAL NO...

Страница 4: ...35 36 LOCAL MODE ONLY OPERATIONS 36 37 REMOTE MODE ONLY OERATIONS 37 40 FAULT DESCRIPTIONS 40 42 MAINTENANCE 43 46 TROUBLESHOOTING GUIDE 43 FAULT TROUBLESHOOTING GUIDE 43 45 PARTS 47 48 HIGH VOLTAGE C...

Страница 5: ...CP 13 05 3...

Страница 6: ...ments etc make such variations inevitable Compare this manual with your system instal lation drawings and appropriate Ransburg equipment manuals to reconcile such differ ences Careful study and contin...

Страница 7: ...g should have flash points equal to or higher than those of the coating material Those solvents used for cleaning must have a flash point at minimum of 5 C 9 F greater than ambient temperature It is t...

Страница 8: ...et Frequent power supply shutdown indicates a problem in the system which requires correc tion Always turn the control panel off prior to flush ing cleaning or working on spray system equip ment Ensur...

Страница 9: ...I or II Division 1 and 2 hazardous areas Refer to NFPA 33 or EN 50 176 Turn the power supply OFF before working on the equipment Test only in areas free of flammable or com bustible material Testing m...

Страница 10: ...use a fire or explosion Parts being sprayed must be supported on conveyors or hangers and be grounded The resistance between the part and ground must not exceed 1 megaohm Reference NFPA 33 or EN 50 17...

Страница 11: ...9060 High Voltage Controller Safety CP 13 05 3 6 N O T E S...

Страница 12: ...signals are provided one for current and one for voltage and can be used to control the set point See the Operation portion of this Manual for more information The REMOTE mode triggering of HV is perf...

Страница 13: ...o room temperature before use Humidity 95 Non Condensing Electrical Input Voltage 100 240 VAC Frequency 50 or 60 Hz Current 1 A max RMS Wattage 40 watts max Output Voltage 20 90kV MAX DC adjustable in...

Страница 14: ...nal Air Flow Switch Hose Connections 3 Reset Button 11 High Voltage Cable Connector 4 A Display 12 Standard I O Connector 5 Fault Indicator 13 Fuses 6 On Off Switch 14 Ground Lug 7 Local Remote Mode I...

Страница 15: ...e This LED is lit when the Controller is in LOCAL mode REMOTE Mode LED Indicator The REMOTE mode LED indicator is a right pointing triangle and is located on the right side the HV control button on th...

Страница 16: ...icates when the unit should be in REMOTE mode When this remote I O signal is active the unit will be in REMOTE mode otherwise the unit will be in LOCAL mode CONNECTION INTERFACE The 9060 Controller co...

Страница 17: ...located directly above the ground lug connection They are present to provide a measure of safety against power surges through the AC input The top fuse holder is connected in series between the HOT li...

Страница 18: ...her an AC or DC signal using the Relay Common Input as the signal source For information regarding the relay contact voltage ratings please refer to the Relay Output Contacts portion of the Installati...

Страница 19: ...alues stored in the 9060 the unit MUST be in LOCAL mode If the voltage setpoint must change between more than 3 values one of the analog KV setpoint signals should be used N O T E Analog Inputs Two 2...

Страница 20: ...an input Although the allowable range for the analog current signal does include 0mA 3mA it will normally be listed as 4 20mA as the 0 3mA portion of the range is insuf ficient to override KV setpoint...

Страница 21: ...ilable in both LOCAL and REMOTE modes This signal being a relay controlled signal can be config ured as either an AC or DC signal using the Relay Common Input as the signal source For information rega...

Страница 22: ...approved applicators should be used with the 9060 High Voltage Controller W A R N I N G DO NOT locate the Controller near or adjacent to heat producing equipment such as ovens high wattage lamps etc...

Страница 23: ...should be made using shielded cable or conduit which is connected to earth ground in a continuous 360 fashion at both ends The best way to do this is to use a connector conduit fitting at each end of...

Страница 24: ...ing and mark 1 span of cable that passes through the connector housing to be stripped to braid See Figure 8 3 Remove cable and strip marked 1 section to cable braid 4 Slide the cable grommet hardware...

Страница 25: ...emoved see Figure 11 4 Install the AC input wiring 0 8mm2 18AWG minimum through the Conduit Adapter Plate using conduit and wire to TB1 as follows In general conduit must be used for approved AC insta...

Страница 26: ...flush the spray ap plicator with high voltage ON as this is a severe fire hazard and risk to personnel safety It is recommended that the high voltage control be interlocked with the sol vent flush si...

Страница 27: ...9060 High Voltage Controller Installation CP 13 05 3 22 Figure 12 Controller Schematic...

Страница 28: ...the high voltage cable it is required to remove it from the spray applicator care should be taken when rein stalling so that the high voltage cable is com pletely engaged The Controller MUST be OFF w...

Страница 29: ...ing used connect the ground green lead from the flow switch to the ground screw on the base plate shown in Figure 13 The trigger signal blue lead should be connected to the trigger signal on the remot...

Страница 30: ...al Sink JMP1 1 3 1 3 JMP1 2 4 4 6 JMP2 2 3 1 2 LOCAL Mode Jumper Settings Figure 15 Local Remote Board Jumper Headers Jumper 1 Jumper 2 5 Secure the cabinet door replace the fuses and reconnect the AC...

Страница 31: ...Signal Loca tions table contains the complete list of all I O ground and 24VDC supply locations as well as their normal voltage current values The locations of the I O terminal blocks are shown in Fi...

Страница 32: ...shielded cable for each conductor to ensure a good connection has been made with each conductor Also a 2 finger pull test should be done Pull on each con ductor with 2 fingers to ensure it is tight N...

Страница 33: ...g be fore reconnecting the 9060 Controller to the AC source 9 Secure the cabinet door replace the fuses and reconnect the AC source 10 Refer to the Operations section of this service manual and use th...

Страница 34: ...fic applicator being used Us ing the wrong configuration may allow for operation outside the recommended pa rameters and values for the applicator and can result in damage or un safe op eration W A R...

Страница 35: ...The LOCAL and REMOTE mode triangle indicators on the left and right side of the mode button are shown in Figure 21 The indicator corresponding to the unit s current operating mode should be lit while...

Страница 36: ...tage is triggered turned on there is a 4 second timer that inhibits the DI DT overload fault while the applicator is being charged Ensure that NO OBJECTS approach the bell dur ing charging W A R N I N...

Страница 37: ...panel or setpoint buttons will now have no affect on the kV setting Figure 22 Lockout Jumper Location Figure 23 Jumper Location Front Panel Lockout Overload The overload circuit may be activated for...

Страница 38: ...ls The third sub mode displays the gun type value and firmware version To enter the remote I O monitoring and diagnostic mode ensure that the high voltage is not activated and press all 3 preset butto...

Страница 39: ...they are listed in the digital index reference table under their respective index Figure 26 Analog Signal Monitoring Index 0 Analog Index Reference Index Analog Signal 0 Buffered Gun Current Feedback...

Страница 40: ...Max Inc Indicators OL Current Overload 20 190 5 Decimal marker on code means overload jumper is installed Hd Startup Holdtime 2 15 seconds 0 5 sec N A Adjustable Parameters SA Sample Time 2 50 1 Avai...

Страница 41: ...rameter has been selected any changes to the value can be saved by pressing the preset 1 button This will save the changes to memory and de select the parameter The saved changes to parameters will im...

Страница 42: ...erate in either Tripleset Selection mode or Analog I O mode By default the unit comes from the factory configured to operate in Tripleset Selection mode Follow the following instructions to modify the...

Страница 43: ...TIMING The analog setpoint signal minimum hold time is 80 ms to allow for analog sampling Output will begin to adjust after the setpoint has been updated ANALOG VOLTAGE SIGNALING Control Signal Range...

Страница 44: ...60 Controller automatically trun cates the maximum setpoint value to the maximum voltage allowed for the applica tor being used Control signal increases beyond the maximum voltage equivalent will have...

Страница 45: ...nit will illuminate a GF indication will show in the uA display This fault will occur if the microprocessor detects a loss of ground at the high voltage section or external cascade If this fault occur...

Страница 46: ...A This fault can be caused by excessive overspray on the ap plicator or a paint formulation that is too con ductive It may also be caused by a bad pc board Clean the applicator check the paint formula...

Страница 47: ...urs reset the Controller If this fault continues to occur replace the main PC board Figure 40 Over Voltage Fault Display Figure 41 Feedback Fault Display DI DT Overload Fault dOL This fault is ONLY ap...

Страница 48: ...UBLESHOOTING GUIDE FAULT TROUBLESHOOTING GUIDE Before troubleshooting gun and control unit problems flush the gun with solvent and purge with air Some of the tests will require high voltage to be appl...

Страница 49: ...Load Fault indicates the current output has exceeded the overload threshold This fault is only active if jumper 17 is shorted The overload threshold is normally set at 10 A below the maximum output of...

Страница 50: ...ntroller 2 Ensure test jumper J8 is not shorted on both posts Ensure that the gun trigger is not pressed or for remote units that the re mote trigger input signal is not active 3 Turn on the voltage c...

Страница 51: ...9060 High Voltage Controller Maintenance CP 13 05 3 46 N O T E S...

Страница 52: ...Part Number Model Selection TABLE A Plug Selection TABLE B Model number and serial number of the voltage controller is located on the left outside face of the main enclosure Table A Model Selection D...

Страница 53: ...6 41 9060 High Voltage Controller PC Mainboard for 80100 21X 31X 41X A13123 00 9060 High Voltage Controller Local Remote Board 79350 01 9060 High Voltage Cascade 79428 00 Power Supply 24V 24VDC Power...

Страница 54: ...0 High Voltage Controller Accessories List Part Description 76652 01 HV Probe 76652 02 Meter w Test Leads 76652 03 Paint Test Probe w Meter 76652 04 Deluxe Kit Include HV Probe Meter w Test Leads and...

Страница 55: ...ear from date of purchase WRAPPING THE APPLICATOR ASSO CIATED VALVES AND TUBING AND SUPPORTING HARDWARE IN PLASTIC SHRINK WRAP OR ANY OTHER NON APPROVED COVERING WILL VOID THIS WARRANTY RANSBURG S ONL...

Страница 56: ...uration uses the following Sourcing Configured Digital Inputs Apply 24VDC to activate the input Permanently Wired into Remote Mode Jumper Wire from TB3 10 to TB3 2 Normally Open NO Contact to Activate...

Страница 57: ...Sourcing Configured Digital Inputs Apply 24VDC to activate the input Permanently Wired into Remote Mode Jumper Wire from TB3 10 to TB3 2 Normally Open NO Contact to Activate Reset when unit is Faulte...

Страница 58: ...e the input Normally Open NO Contact to Activate Reset when unit is Faulted Normally Open NO Contact to Activate HV Trigger to turn on HV Cascade Normally Open NO Contact to Activate remote mode Turn...

Страница 59: ...ng Sinking Configured Digital Inputs Apply GND to activate the input Permanently Wired into Remote Mode Jumper Wire from TB3 11 to TB3 2 Normally Open NO Contact to Activate Reset when unit is Faulted...

Страница 60: ...l Service Assistance 320 Philips Ave Toledo Ohio 43612 1493 Telephone toll free 800 233 3366 Fax 419 470 2233 Form No CP 13 05 3 2013 Ransburg All rights reserved Litho in U S A Models and specificati...

Отзывы: