9060 High Voltage Controller - Introduction
CP-13-05.3
14
can be configured as either all sourcing or all
sinking inputs. For information regarding
configuring
the
inputs,
refer
to
the
“Installation”
section
of
this
manual.
Local/Remote Mode Signal
The local/remote mode signal (TB3-2)
indicates to the 9060 Controller whether the
system is currently in LOCAL mode or
REMOTE mode. If the signal is off, the
system will be in LOCAL mode. If the signal
is on, the system will be in REMOTE mode.
Reset Signal
The reset signal (TB3-1) will reset any fault
or overload condition that has occurred. It
will
NOT
prevent any other existing fault
conditions from re-faulting the system
immediately after resetting. Please refer to
the “Operation” section of this service
manual for fault reset and troubleshooting
information.
Remote Trigger Signal
The remote trigger signal (TB3-5) is used to
indicate to the 9060 Controller to turn on the
high voltage.
Tripleset Signals
(Setpoint 0 and Setpoint 1)
The tripleset signals, Setpoint 0 and Setpoint
1 (TB3-3 and TB3-4), are a pair of signals
that are used to select one of the three
Setpoint 1 Setpoint 0
Selection
0 (off)
0 (off)
No Change
0 (off)
1 (on)
Preset 1
1 (on)
0 (off)
Preset 2
Triple Set Combinations
1 (on)
1 (on)
Preset 3
The tripleset signals can be used to se-
lect a preset from the three (3) preset volt-
ages. The preset values can
NOT
be ad-
justed from REMOTE mode. To adjust
the preset values stored in the 9060, the
unit
MUST
be in LOCAL mode. If the
voltage setpoint must change between
more than 3 values, one of the analog KV
setpoint signals should be used.
N O T E
Analog Inputs
Two (2) analog input signals, along with an
analog common input, are provided on the
9060 High Voltage Controller for analog
control the KV setpoint value. One signal is
provided for analog control using a voltage
signal, the other for a current signal. The
analog inputs are intended for applicator
systems that require either more than 3
presets or an adjustable setpoint voltage.
These signals can only be used when the
preset voltages that are normally selected
during LOCAL mode operation via the three
preset buttons on the left side of the front
panel. The two signals are used together as
a binary number to select the corresponding
preset value. The selected preset value will
not change unless a different preset value is
input. The binary combinations and their
resulting selection are listed in the Triple Set
Combinations table. These signals can only
be used when the Remote Mode Configura-
tion is set to disable Analog Control. For
more information on how to configure
Remote Mode, please see the Operation
section of this service manual.
Sinking and Sourcing refers to the sig-
nal that is applied to activate an input. If
you are applying a +24 VDC signal to the
input to activate it, you are sourcing. If
you are applying a GROUND signal to the
input, you are sinking.
N O T E
There is a
5 second
fault reset delay
timer that
inhibits
the triggering of high
voltage immediately after a fault reset.
N O T E
Содержание 80100 Series
Страница 2: ...CP 13 05 3...
Страница 5: ...CP 13 05 3...
Страница 11: ...9060 High Voltage Controller Safety CP 13 05 3 6 N O T E S...
Страница 27: ...9060 High Voltage Controller Installation CP 13 05 3 22 Figure 12 Controller Schematic...
Страница 51: ...9060 High Voltage Controller Maintenance CP 13 05 3 46 N O T E S...