RAM 100 • 1000 • 5500
Dip Switch “A”
Dip Switch “B”
Dip Switch “C”
“Intelligate” Control Board
Figure 17
DIP SWITCH CONFIGURATION
DIP SWITCH S4 - “A”
DIP SWITCH “A” 4 - LEFT/RIGHT
OFF Left-hand installation
ON Right-hand installation. Reverses the motor and limit
wires without moving any wires.
B1 - PREWARN
OFF Normal operation
ON
Triggers the relay on JP2, pins 7 & 8, for 3 seconds
before the gate moves in any direction.
B2 - CONSTANT WARN
OFF Normal operation
ON
Triggers the relay on JP2, pins 7 & 8
B3 - SECURE CLOSE
OFF Normal operation
ON
When power is lost and then regained, if all devices are
clear and it’s safe, the gate will close.
B4 - SECURE OPEN
OFF Normal operation
ON
If the gate comes off of the limit without a valid
command, the gate will re-open.
B5 - ONE PASS
OFF Normal operation
ON
While the gate is opening, if the safety input is triggered
and then cleared, the gate will immediately start
closing. If the safety input is then activated again,
before the gate is fully closed, the gate will stop and
stay at rest until the safety loop is cleared. At any time
if a valid open signal is received, the gate will open.
B6 - CLOSE DELAY
OFF Normal operation
ON
Adds a 1 second delay before the gate closes.
B7 - OPEN DELAY
OFF Normal operation
ON
Adds a 1 second delay before the gate opens.
B8 - RADIO CYCLE
OFF
Gate will open, if on the close limit, and close, if on
the open limit. If in travel, the gate will always open or
continue to open.
ON
Gate will open, if on the close limit, and close, if on the
open limit. If in travel, the gate will stop with the first
command and then reverse with a second command.
DIP SWITCH “A” 1, 2 & 3;
AUTOMATIC TIMER TO CLOSE GATE
‘0’ is “OFF”
‘1’ is “ON”
Switch 1 2 3
Gate Open Duration:
0 0 0
Disabled
0 0 1
00 Seconds
0 1 0
5 seconds
0 1 1
10 seconds
1 0 0
15 seconds
1 0 0
30 seconds
1 1 0
45 seconds
1 1 1
60 Seconds
DIP SWITCH S6 - “B”