Weather Center II User Manual
Rain Master Irrigation Systems
Page 34
5.1.3 Rain Fall Sensor Installation
The housing of the Rain Fall Sensor should be level. After installation is
complete, check to make sure that the Rain Fall sensor is not held in a
dead center position by pressing either end down against the stop.
5.1.4 Rain Fall Sensor Information
Accuracy:
1.0% at 2 inches per hour or less.
Maintenance: Occasional cleaning of debris from the filter
screen may be required.
5.1.5 Rain Fall Sensor Interface
The two wires from the Rain Fall sensor are connected to Input 3
( + ) and Input 3 ( - ) of the Sensor Terminal board. It does not matter
which wire goes to which terminal. This is depicted in Figure 11 -
Evolution DX2 Wiring Detail.