Weather Center II User Manual
Rain Master Irrigation Systems
Page 44
1
4
If voltage reads greater than +5
VDC, reconnect
the two wires to the Sensor
Terminal board Inputs 2(+) and
2(-). If voltage reads 0,
check for
open/shorts in cable and
terminal block connections.
End
5
Can +5 VDC be
measured at terminal
inputs 2(+) and 2(-) of the
Sensor Terminal
Board?
Disconnect the two
wires from the Sensor
Terminal at terminals
Input 2(+) and Input
2(-) and re-measure
voltage. If voltage
reads 0, contact the
factory. If voltage
reads +5VDC, the
problem is in the wiring
Note:
If the Flow Max feature (Evoution DX2 only) is utilized on
the controller that the Weather Center is connected to, then
the user must say Flow Meter is connected to this
controller. During the Flow Max Set-Up (Refer to DX2
User Guide pages F-22 & F-23) the “K” and offset values of
“0” must be entered at the sub master (Refer to DX2 User
Guide).
Содержание Weather Center II
Страница 1: ...Weather Center II User Manual Part 500009 Rev D...
Страница 2: ...Weather Center II...
Страница 3: ......
Страница 7: ......
Страница 17: ...Weather Center II User Manual Rain Master Irrigation Systems Page 10 Figure 4 Eyebolt Assembly Procedure...
Страница 20: ...Rain Master Irrigation Systems Weather Center II User Manual Page 13 Figure 7 Weather Center Tower Mounting...
Страница 23: ...Weather Center II User Manual Rain Master Irrigation Systems Page 16 Figure 9 Weather Center Terminal Access...
Страница 25: ...Weather Center II User Manual Rain Master Irrigation Systems Page 18 Figure 11 Evolution DX2 Wiring Detail...
Страница 65: ...3910 B Royal Avenue Simi Valley California 93063 Telephone 805 527 4498 Fax 805 527 2813 www rainmaster com...