Weather Center II User Manual
Rain Master Irrigation Systems
Page 46
If voltage reads +8 VDC, reconnect the
two wires to the Sensor Terminal board
Inputs 3+ and 3-. At the tower terminal
block, unplug the rain gauge connector.
Re-measure voltage at terminals Input
3+ and 3-. If voltage reads +8 VDC,
problem lies in rain gauge. If voltage
reads 0, check for shorts in cable and
terminal block connections.
4
1
1
End