Chapter 3 Mounting and Installation
Table 2 - Master Valve and Pump Wiring Options
*
No SETUP programming required (factory default settings).
NOTE:
Option 2 shows that a pump is used in the program, the SETUP
programming indicates that the PUMP should not be programmed. This
preserves Station 1 as a station output.
WARNING: ALWAYS TURN-OFF POWER before changing or modifying field, senor
or power wiring within the controller. Dangerous voltage and current exist
within the controller which may damage the controller if improperly
connected or shorted.
3.2.1.1 Electrical Connections for a Master Valve
The RME EAGLE allows you to select the type of Master Valve (MV), either a Normally Open or
Normally Closed configuration.
When the Master Valve is a Normally Closed configuration, the Master Valve line on connector J4
is supplying 24 VAC power. The power is available to this connection whenever any station in the
controller is on.
For Normally Open Master Valves, the controller supplies 24 VAC only when there is a Main Line
Fault or Unscheduled Flow Fault detected.
WARNING: ALWAYS TURN-OFF POWER before changing or modifying field, senor
or power wiring within the controller. Dangerous voltage and current exist
within the controller which may damage the controller if improperly
connected or shorted.
Option Normally
Closed
Master
Valve
Normally
Open
Master
Valve
Pump
Used
Reference
Wiring
Figure
SETUP
Master Valve
Usage per
Program
SETUP
Master
Valve
Type
SETUP
Pump Usage
per Program
1*
9
—
Never
5
1, 2, 3, 4
NC
None
2*
9
—
Always
6 or 7
1, 2, 3, 4
NC
None
3
9
—
Sometime
8
1, 2, 3, 4
NC
As Needed
4 —
9
Never
5
1, 2, 3, 4
NO
None
5 —
9
Always
6 or 7
1, 2, 3, 4
NO
1, 2, 3, 4
6 —
9
Sometime
9
1, 2, 3, 4
NO
As Needed