Chapter 9 Troubleshooting
Page 109
Table 9 - Troubleshooting Assistant
Symptom
Action
Display is blank
1. Ensure controller has power and all wires are properly
connected.
2. Check secondary voltage of transformer for 24 VAC.
No stations turn on
automatically
1. Is the controller in Automatic Mode?
If No –
Press:
2. Ensure the Rain Switch is in the “Auto Watering” position.
3. Does
Ã
appear in left most position of display? Yes - Rain
Sensor is enabled and is reading a wet condition (see SETUP).
4. Does appear in left most position of display? If Yes –
Odd/Even Watering is enabled and today is a non-watering
day (See SETUP).
5. Ensure that the Master Valve, Pump wiring and setup is
correct.
6. Activate Manual System Check. If station turns on, review
programs:
• Water Days
• Station Runtimes
• Percentage Valid
• Start Times
Display alternates with
FAULT…PRESS…REVIEW
A problem with either flow or station field wiring has occurred.
A station remains on
Place Rain Switch in “No Watering” position.
If station remains on then:
• Check for dirt in valve’s solenoid which will cause the
solenoid to stick.
• Check for obstructions in valve, or torn diaphragm.
If station goes off then:
• Check station’s programmed watering time.
• Check program percentage.
QUIT