background image

Turn off LDI wire path slide 

switches. Cycle LDI Power Switch 

from OFF to ON.

Turn on each wire path one at a 

time. After 10 seconds, verify no 

“Flicker” on Field LED.

If visible on Field LED, open 

Decoder Diagnostics window in 

central control software.

Activate 50/60Hz mode test.

The wire with the higher 

draw will have leakage.

Choose point halfway 

between measurement point 

and end of wire path. Retest.

Repeat this method to narrow 

down location of damaged 

insulation and leakage to 

ground. Repair as necessary.

Verify “at rest” current draw.

Using a clampmeter, at the 

downstream (field) side of the 

mSP-1, compare the mA draw 

of RED and BLACK wires.

Choose point halfway 

between measurement point 

and central control. Retest.

when repairs are complete, 

verify “at rest” current draw 

matches expected current draw.

Run ON/OFF test to validate 

system operation.

At LDI, disconnect wire with lower 

draw and choose point halfway 

to end of wire path. measure 

draw in connected (active) wire. 

Disconnect any critical path loops 

before testing.

Severity of Ground Fault 

can vary based on soil 

moisture content.

START

Visually check Field LED on 

LDI/SDI for clean alteration 

from RED to GREEN at  

0.5 second intervals.

Recommended Rain Bird

®

 

Troubleshooting Procedure for 

“Suspected Ground Fault” 

(Leakage to Ground)

Symptoms: 

Lower run times or zeros 

in the course log. Fluctuating current 

reported in Decoder Diagnostics. No 

clean alternating color in  

Field LED on LDI/SDI.

NOT CLEAN

CLEAN

FLICKER

HIGH

Replace LDI

If wire Path is 

Activated, Consider 

Possibility of Ground 

Fault on Path

No Further Action.

NOT CLEAN

DRAw CLOSE 

TO ZERO

VALIDATED

DRAw GREATER 

THAN ZERO

Normal systems should 
expect “at rest” current 
draw to fluctuate 
between 2 mA – 5 mA.

7

Содержание FD-101

Страница 1: ...llation requires up to 80 percent less wire than conventional controller systems Electronic components are completely encapsulated to protect against the elements And system expansion is easy simply s...

Страница 2: ...mine the total calculated current draw of the wire path 3 To calculate the static current draw of an entire interface add up all calculated wire path current draws that are connected to the interface...

Страница 3: ...d wire path with short condition LED will be solid when shorted wire path is activated Disconnect field wires and recheck voltage Reconnect field wire Compare expected and actual at rest current draw...

Страница 4: ...ION DETAILS Large and small Decoder Interface Locating a bad decoder using a Clamp meter SENSOR 1 e g Rain Sensor SENSOR 2 Not Shown e g Alarm Sensor To System Ground Connect to 24 VAC transformer Dur...

Страница 5: ...t Run ON OFF Test in Decoder Diagnostics to Validate System Operation Repeat to narrow down location of wire path short Choose point halfway between measurement point and end of wire path Break critic...

Страница 6: ...determine exact location of broken wire or partial connection Bad Splice Turn on first wire path Compare expected actual at rest current draw to expected current draw in Decoder Diagnostic window in c...

Страница 7: ...fy at rest current draw matches expected current draw Run ON OFF test to validate system operation At LDI disconnect wire with lower draw and choose point halfway to end of wire path Measure draw in c...

Страница 8: ...Corporation 6991 East Southpoint Road Tucson AZ 85756 U S A Phone 800 984 2255 520 741 6100 Fax 520 741 6522 Email rbgolf rainbird com Technical Service and Support 800 RAINBIRD U S and Canada only R...

Отзывы: