![background image](http://html.mh-extra.com/html/radionics/d9210b/d9210b_program-entry-manual_780454006.webp)
ACCESS
Door Profile
32207C 3/97
D9210B Program Entry Guide
© 1997 Radionics
Page 6
D# Fire Unlock?
Default:
No
Selections:
Yes or No
Use this program item to activate the relay for the door strike and shunt the
door zone automatically upon a Fire Alarm. This command will override a
Secure door and Locked Door state. The relay will activate for all doors with
this prompt programmed YES when a Fire Alarm occurs in any area.
Yes -------- Relay will activate and shunt will be applied for the door contact
automatically upon a Fire Alarm.
No ---------- Door will remain in its current mode upon a Fire Alarm.
Warning: This will unlock the door regardless of the armed state.
D# DisarmOn Open?
Default:
No
Selections:
Yes or No
Use this program item to determine whether the door needs to be physically
opened prior to disarming the area upon a valid access request. The user
initiating the access request must have access levels that allow disarming with
ID.
Yes -------- The area will disarm only after the door has been opened for a user
with a valid disarm level.
No ---------- The area will disarm whether or not the door has been opened as
soon as a user with a valid disarm level has presented a valid
token/card.