ACCESS
Strike Profile
32207C 3/97
D9210B Program Entry Guide
© 1997 Radionics
Page 8
D# Extend Time
Default:
10
Selections:
Blank, 1 - 30 Seconds
Enter the amount of time that strike, buzz and shunt activation will be prolonged
if a door is left open and the shunt time expires. At the end of the programmed
extend time, the buzzer will continue to buzz until the door is closed. In addition,
if programmed, the point assigned to the door will indicate a Trouble, Alarm or
Fault at the command center.
NOTE: [CLOSE DOOR #] display on Command Center will not activate if no
time (blank) is programmed.
D# Deact On Open?
Default:
Yes
Selections:
Yes or No
This program item determines whether the strike will deactivate immediately
upon physically opening the door.
Yes -------- Strike will deactivate when the door is opened after a valid access
granted request.
No ---------- Strike will remain activated for the amount of the programmed
strike time whether door is opened or closed.
Programming Tip: In order for this function to work, a point needs to be
assigned to the door.
TO REDUCE FALSE ALARMS: We recommend that you maintain this
programming item as defaulted (YES). This will help prevent the door from
“bouncing” open and causing a false alarm.
D# RTEShunt Only?
Default:
No
Selections:
Yes or No
Use this program item to disable the strike, but still activate the programmed
shunt time upon a Request to Enter an area.
Yes -------- Programmed shunt time will activate so door can be manually
opened.
No ---------- Request to Enter (RTE) automatically activates the programmed
strike and shunt time.
Application Tip: Use this parameter when a user can open a door manually
without relying on a token/card to activate the strike (such as with a “push bar”).
NOTE: When RTEShunt Only is “Yes,” Request To Enter events are not
logged, reported, or printed.