2. FIRST START-UP
SER
VICE
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P12
HEATING FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE
FAN MINIMUM SPEED IN HEATING PHASE, THAT
CORRESPONDS TO THE MINIMUM BURNER POWER
DURING A REQUEST TO OPERATE IN HEATING
MODE. THE VALUE IS PRE-SET BASED ON THE SET
POWER (SEE PARAMETER P00) AND ON THE GAS
TYPE (SEE PARAMETER P02).
(CHANGE THE PARAMETER VALUE ON BOTH
CONTROL PANELS, MASTER AND SLAVE, PLEASE
SEE CHAPTER "PARAMETER ACCESS AND
PROGRAMMING").
SEE CHAPTER ‘HEAT
CAPACITY DIAGRAM (KW) –
ELECTRIC FAN FREQUENCY
(HZ)
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P13
HEATING FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE
FAN MAXIMUM SPEED IN HEATING PHASE, THAT
CORRESPONDS TO THE MAXIMUM BURNER POWER
DURING A REQUEST TO OPERATE IN HEATING
MODE.
THE VALUE IS PRE-SET BASED ON THE SET POWER
(SEE PARAMETER P00) AND ON THE GAS TYPE (SEE
PARAMETER P02).
(CHANGE THE PARAMETER VALUE ON BOTH
CONTROL PANELS, MASTER AND SLAVE, PLEASE
SEE CHAPTER "PARAMETER ACCESS AND
PROGRAMMING").
SEE CHAPTER ‘HEAT
CAPACITY DIAGRAM (KW) –
ELECTRIC FAN FREQUENCY
(HZ)
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P14
STARTING STEP ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE
FAN SPEED DURING START-UP
THE VALUE IS PRE-SET BASED ON THE SET POWER
(SEE PARAMETER P00) AND ON THE GAS TYPE (SEE
PARAMETER P02).
(CHANGE THE PARAMETER VALUE ON BOTH
CONTROL PANELS, MASTER AND SLAVE, PLEASE
SEE CHAPTER "PARAMETER ACCESS AND
PROGRAMMING").
SEE CHAPTER ‘HEAT
CAPACITY DIAGRAM (KW) –
ELECTRIC FAN FREQUENCY
(HZ)
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)