Note
This behaviour comes from the RipEX functionality where UDP is a preferred transport
solution. In case of celullar networks, TCP might be a better solution. When implementing
this solution into your network, you might configure Modbus TCP on the remote
M!DGE/MG102i (not a unit locally connected via Ethernet) causing the TCP session to be
between a local device and remote M!DGE/MG102i instead of UDP. The final conversion
from TCP to UDP so the Protocol server listening on the UDP port 8882 by default is done
at the remote unit afterwards. In such a case, make a Translation rule which sends all re-
ceived packets to the localhost.
Important
In some Modbus TCP implementations, Unit ID field within the datagram is always set to
"FF". In such a case, you can use the "Replace PLC address" option so that the Unit ID is
replaced by some Modbus RTU address. Thanks to this parameter, regular Mask/Table
address translation can be used. Consider carefully where you put the corresponding
parameter (local or remote M!DGE/MG102i and if placed in Modbus TCP or Modbus RTU
Protocol server menu - it can be set at both places, but not simultaneously).
See the Application note for more details and examples.
Administrative status
Enable or disable the feature.
My TCP Port
The TCP port for a session with local Modbus TCP Master. It can also
be a remote Modbus TCP Master resulting in a TCP session over the
cellular network instead of UDP.
TCP inactivity [s]
The TCP inactivity timeout in seconds.
Transport protocol
The transport protocol used, must be set to UDP only.
125
© RACOM s.r.o. – MG102iGPRS/UMTS/HSPA+/LTE router
Web Configuration
Содержание MG102i
Страница 2: ......
Страница 147: ...147 RACOM s r o MG102iGPRS UMTS HSPA LTE router Web Configuration...
Страница 148: ...7 8 LOGOUT Log out from Web Manager MG102iGPRS UMTS HSPA LTE router RACOM s r o 148 Web Configuration...
Страница 174: ...174...