Tipically the distribution board contains the thermal-magnetic circuit breakers for
each amplifier included in the system and one for service.
WARNING: Electric shock hazard! Never handle the RF output connector
when the equipment is powered on and no load is connected. Injury or death
may result.
Ensure that the distribution board of the transmitter is set to “OFF”.
5.1.3 Device power supply connections
Provide for the following (applicable to operating tests and putting into service):
√
Single-phase 230 (-15% / +10%) Vac mains power supply for
TEX3500LCD
,
with adequate earth connection.
√
For operating tests only: dummy load with 50 Ohm impedance and adequate
capacity (minimum 3500W per
TEX3500LCD
).
Note:
to ensure the safety of the operators, carry out the wiring according to the
laws and regulations in force in the country where this equipment is installed.
Check that the
POWER
switch on the front and rear of
TEX3500LCD
is in the
“
OFF
” position.
Connect the mains power cable to the MAINS connector on the rear panel.
Attention:
Be sure to connect the equipment correctly, to
avoid the risk of
damaging
. It is necessary connect the ground conductor of the power supply
cable to the specific terminal in the multipole socket and check the efficiency of
your own grounding system.