43
3.6 ALARM
LANGUAGE: ENGLISH
INFORMATION
[DOME SETTINGS]
MOTION
RESTART
FACTORY DEFAULT
EXIT
MAIN MENU
IR LED
WIPER
IDLE
[ALARM]
ADVANCED
OTHERS
BACK EXIT
DOME SETTINGS
ALARM NO. : 1
CONTACT: N/O
ALARM MODE: OFF
ACTION: NONE
ALARM OUT: OFF
RESET DELAY: 10 SEC
BACK EXIT
ALARM SETTING
The dome system has 4 alarm inputs and 2 alarm outputs
(optional function). When an alarm signal is received to the
input of the dome it triggers a user defined action (such as a
presets, patterns, etc.), at the same time the alarm output
signal will be activated.
1. ALARM NO.:
Move the cursor to
‘ALARM NO.’ Click
IRIS + to enter and click up or down button to select the
alarm input no.
2. CONTACT:
Set the alarm contact status. There are two
input states, OPEN and CLOSE.
3. ALARM MODE:
OFF
Alarm function is deactivated.
ON
Alarm function is activated.
AUTO
AUTO Alarm function will be activated and
deactivated between START TIME and STOP
TIME.
4. ACTION
: Set the alarm action:
NONE
(default) No action
PRESET
Dome goes to preset. (Default as Preset 1)
SCAN
Dome starts auto scan (Default as Auto
Scan 1)
SEQ
Dome runs auto cruise (Default as Auto
Cruise 1)
PATTERN
Dome runs pattern (Default as Pattern 1)
ALARM OUT:
Move the cursor to
‘ALARM OUT’. Click IRIS
+ to enter and click up or down button to select one of the
alarm output channel options
“OFF” “OUTPUT1”
“OUTPUT2” “ALL”, which are used to set the link alarm
output signal switch after receiving alarm input signal(s).
RESET DELAY:
Move the cursor to the
‘ALARM OUT’. Click
IRIS + to enter and click up or down button to select a reset
delay time:
“10SEC” “30SEC” “1MIN” “5MIN” “10MIN”. This
settings dictates the length of time that the speed dome has
from alarm signals detection to alarm reset and return back
to normal. The setting is valid under AUTO ALARM MODE.