Analysis of operation of each control:
Electric lock function:
-
When the doors are set to operate automatically
(AU)
the electric lock is always active at
minimum voltage
-
When the doors are set to night operation
(NI)
, the electric lock is deactivated when closing
is complete, thus mechanically locking the door
OPEN KEY command operation:
This command can be activated at any time with various conditions:
-
With parameter I=0, one impulse opens and one impulse closes
-
With parameter I=from 1 to 9 sec. the first impulse opens, followed by
closing after the selected time
STOP command operation
Safety with contact NC (normally closed). This safety is always active. When this contact is
opened, the door is immediately stopped. When the contact is restored, the first manoeuvre is
accepted, again performing a realignment cycle using OPEN KEY or INTERNAL RADAR or
EXTERNAL RADAR. The operating status selected by the user is then restored
Operation of FSW1 Photocell 1 safety
Safety with contact NC (normally closed). Active only during closure. As soon as the contact is
opened, the direction of movement is immediately reversed. If activated with the door open, it
remains stopped for the pause time for automatic closure
Operation of FSW2 Side sensor
Safety with contact NC (normally closed), with different operating modes based on door status:
A.
If stopped during closing, one impulse will perform full opening at deceleration speed.
B.
If stopped during opening, it keeps the door open and prevent automatic closing if in
automatic mode
(AU)
C.
If it is closing it travels its entire distance in slow motion
RADAR INT operation
OPEN command with various reactions based on the selected operating status:
A Night function 1=enabled
Î
no operation
B total open = with doors closed performs opening, if activated with doors open, resets the
automatic closure time
C partial open = with doors closed performs opening, if activated with doors open, resets the
automatic closure time
RADAR EXT operation
OPEN command with various reactions based on the selected operating status:
A Night function 1=enabled
Î
no operation
B total open if selected operating status RI
Î
no effect
If selected AU or AP
Î
with doors closed performs opening; if activated
with door open, resets the automatic closure time
C partial open if selected operating status RI
Î
no effect
If selected AU or AP
Î
with doors closed performs opening; if activated
with door open, resets the automatic closure time
Содержание WINNY LIGHT
Страница 5: ...5 E N G L I S H 4 SPACE REQUIRED VERTICAL SECTION ...
Страница 6: ...6 VERTICAL SECTION WITH CRASH BAR ...
Страница 7: ...7 E N G L I S H VERTICAL SECTION WITH COMMERCIAL PROFILES COMMERCIAL PROFILE COMMERCIAL PROFILE ...
Страница 27: ...27 E N G L I S H ...
Страница 28: ......
Страница 29: ...I T A L I A N O manuale d u s o e m a n u t e n z i o n e AUTOMAZIONE PER PORTE SCORREVOLI Winny ...
Страница 33: ...5 I T A L I A N O 4 SPAZI RICHIESTI ...
Страница 34: ...6 ...
Страница 35: ...7 I T A L I A N O ...
Страница 55: ...27 I T A L I A N O ...