Chapter 1 Library Specifications and Site Requirements
Site Requirements
8
Quantum|ATL 7100 Series Facilities Planning and Installation Guide
Table 4 Library Floor
Space Requirements
Floor Leveling
1
The floor must be level to within 1/4” over a 6' x 6' area.
Floor Loading
1
A standard raised computer floor rated at 250 lb./ft
2
is sufficient to
support a fully loaded library.
Floor Clearance
1
The cabinet has a nominal floor clearance of 0.75" (1.9cm).
Power
1
The library’s auto-ranging motor and logic power supplies will
accept single phase, 90-264VAC input power at 47-63 Hz.